首页 | 本学科首页   官方微博 | 高级检索  
     


Development and performance of steam ejector refrigeration system operated in real application in Thailand
Affiliation:1. Department of Mechanical Engineering, Isfahan University of Technology, Isfahan 84156-83111, Iran;2. Department of Mechanical Engineering, University of California, Riverside, CA 92521, USA
Abstract:This paper presents the design and construction of a prototype steam ejector refrigeration system which can be operated under the actual condition of Thai environment, which is rather hot and humid. The prototype refrigerator was designed to produce a cooling capacity of approximately 3 kW. Water was selected to be used as the working fluid. The steam boiler used was a vertical fire tube type and it was designed to be used with LPG compact gas burner. The condenser was cooled by water obtained from a conventional cooling tower. The prototype refrigerator was used to produce chilled water which was used to cool a small tested room. It was observed that the room temperature of 24.2 °C was obtained at the cooling load of 3000 W. The cooling water was supplied to the condenser at about 30 °C. The COP obtained was 0.45. This prototype refrigerator is proven to be practical and can be used in actual environment of Thailand.
Keywords:Steam  Ejector  Jet refrigeration  CFD  Chiller  Air-conditioning  Vapeur  Ejecteur  Réfrigération par jet  CFD  Refroidisseur  Conditionnement d'air
本文献已被 ScienceDirect 等数据库收录!
设为首页 | 免责声明 | 关于勤云 | 加入收藏

Copyright©北京勤云科技发展有限公司  京ICP备09084417号