500 kV同杆架设线路感应电流的计算
引用本文:魏旭,李长益. 500 kV同杆架设线路感应电流的计算[J]. 华东电力, 2000, 28(3): 7-10
作者姓名:魏旭  李长益
作者单位:江苏省电力试验研究所,江苏,南京,210029;江苏省电力试验研究所,江苏,南京,210029
摘    要:介绍了利用EMTP程序对不换位的短距离500kV同杆线路的各种工况和线路部分同杆架设条件下感应电流进行的计算.通过对扬州第二发电厂-江都变500kV同杆线路感应电流的计算,指出扬江线两侧现有的接地刀闸将不能满足检修时开断的要求.

关 键 词:500kV同杆线路  EMTP  感应电流  接地刀闸
文章编号:1001-9529(2000)03-0007-04
修稿时间:2000-01-12

Computation of Induction Current in 500 kV Double Circuit
WEI Xu,LI Changyi. Computation of Induction Current in 500 kV Double Circuit[J]. East China Electric Power, 2000, 28(3): 7-10
Authors:WEI Xu  LI Changyi
Affiliation:Jiangsu EPTRI Nanjing 210029
Abstract:The computation of induction current of short distance, non conversion 500 kV lines on same tower under various operating conditions by means of EMTP program is described through the computation of induction current of Yangzhou No.2 Power Plant Jiangdu 500 kV lines on same tower showed that the existing grounding switchgear at both side of the line will not satisfy the requirement for open and close of the line during maintenance.
Keywords:kV lines on same tower EMTP induction current grounding switchgear  
本文献已被 CNKI 万方数据 等数据库收录!