首页 | 本学科首页   官方微博 | 高级检索  
     

红外测温技术在变压器高压套管故障诊断的应用
引用本文:陈仁刚,杨荣华,菅有为,崔勇.红外测温技术在变压器高压套管故障诊断的应用[J].山东电力技术,2013(2):59-61.
作者姓名:陈仁刚  杨荣华  菅有为  崔勇
作者单位:山东电力集团公司检修公司
摘    要:基于红外测温原理,介绍红外测温技术在电气设备故障诊断中的应用,并结合案例分析一起经红外测温发现的500 kV主变高压套管渗油缺陷。通过红外测温仪检测到套管上下部位出现温度分层现象,得出套管发生内渗而导致缺油缺陷的结论,现场解体检查验证分析结果的正确性和有效性,并针对此案例提出相应的预防性措施。

关 键 词:红外测温  高压套管  渗油缺陷  状态检修

Application of Infrared Thermometry Technology for the Fault Diagnosis in Transformer HV Bushing
Abstract:Based on the principle of infrared temperature measurement,the application of infrared thermometry technology in electrical equipment fault diagnosis is introduced in the paper,and combined with case,an oil leakage accident of a high voltage bushing in 500kV transformer is anglicized.Based on the temperature stratification phenomenon which detected by infrared thermometer between upper and lower parts of the bushing,intravasation of the bushing is concluded,scene disintegration check verified the correctness and validity of the analytical results,for the oil leakage problem,the preventive measures are put forward,which provides important technical support for condition-based maintenance.
Keywords:infrared temperature measurement  high voltage bushing  intravasation  condition-based maintenance
本文献已被 CNKI 等数据库收录!
设为首页 | 免责声明 | 关于勤云 | 加入收藏

Copyright©北京勤云科技发展有限公司  京ICP备09084417号