首页 | 本学科首页   官方微博 | 高级检索  
     

电子式互感器误差校准的研究
引用本文:周力任,潘洋,朱力,詹国钟.电子式互感器误差校准的研究[J].电测与仪表,2014,51(22).
作者姓名:周力任  潘洋  朱力  詹国钟
作者单位:上海市计量测试技术研究院,上海,201203
基金项目:国家质量监督检验检疫总局资助项目
摘    要:电子式互感器是智能电网建设的关键设备之一,其性能直接影响到数字化变电站的安全和经济效益,也是电能计量准确的必要条件。电子式互感器的输出与传统互感器不同,分为数字输出和模拟输出两种,因此传统的互感器校准方法已经不适用于校准新型的电子式互感器。文章以模拟量输出的互感器为例,创新性地提出了采用精密分流器和示波器测量比值差和相位差,并对校准数据进行了验证,测量结果满意。

关 键 词:电子式互感器  比值差  相位差  校准  测量
收稿时间:2014/7/14 0:00:00
修稿时间:2014/7/14 0:00:00

Research on Electronic Instrument Transformer Error Calibration
ZHOU Li-ren,PAN Yang,ZHU Li and ZHANG Guo-zhong.Research on Electronic Instrument Transformer Error Calibration[J].Electrical Measurement & Instrumentation,2014,51(22).
Authors:ZHOU Li-ren  PAN Yang  ZHU Li and ZHANG Guo-zhong
Affiliation:Shanghai Institute of Measurement and Testing Technology,Shanghai Institute of Measurement and Testing Technology,Shanghai Institute of Measurement and Testing Technology,Shanghai Institute of Measurement and Testing Technology
Abstract:Electronic instrument transformer is one of the key equipments for the construction of smart grid, of which performance directly influences safety and economic benefit of digital substation and the necessary condition of accurate power measurement. The output signal of electronic instrument transformers is different from that of conventional electromagnetic transformers, which is classified into digital output and analogue output. Therefore, conventional calibration methods are not suitable for testing electronic instrument transformers. This paper takes electronic instrument transformer with analogue output as example; innovatively put forward employing precise shunt and oscilloscope to measure ratio error and phase displacement. Meanwhile, the data were verified and the results were satisfied.
Keywords:electronic instrument transformer  ratio error  phase displacement  calibration  measurement
本文献已被 CNKI 万方数据 等数据库收录!
点击此处可从《电测与仪表》浏览原始摘要信息
点击此处可从《电测与仪表》下载全文
设为首页 | 免责声明 | 关于勤云 | 加入收藏

Copyright©北京勤云科技发展有限公司  京ICP备09084417号