首页 | 本学科首页   官方微博 | 高级检索  
     

并联有源滤波器的一种高可靠性控制策略
引用本文:杨新华,谢兴峰,马建立,丁海昌,裴喜平.并联有源滤波器的一种高可靠性控制策略[J].电力系统自动化,2015,39(5):128-133.
作者姓名:杨新华  谢兴峰  马建立  丁海昌  裴喜平
作者单位:1. 兰州理工大学电气工程与信息工程学院,甘肃省兰州市,730050
2. 北京京仪椿树整流器有限责任公司,北京市,100040
摘    要:为了提高有源电力滤波器的可靠性,针对负载电流波动和负载突停等工况时导致直流侧电压波动过大而无法正常补偿谐波等问题,研究了一种基于多同步坐标旋转的直接谐波提取方法,并将d-q谐波提取方法和直接谐波提取方法对直流侧电压控制的影响进行了分析和对比。提出了把直接谐波提取方法和复合重复控制相结合的指定次补偿控制策略,该策略不仅由于采用直接谐波提取保证了系统的可靠性,与复合重复控制结合也保证了系统的动态性能和稳态精度,而且可以指定次谐波补偿,补偿灵活。仿真和实验结果证明了研究内容的有效性。

关 键 词:有源电力滤波器  高可靠性  复合重复控制  直接谐波提取  指定次谐波补偿
收稿时间:2014/8/12 0:00:00
修稿时间:2014/11/2 0:00:00

A High-reliability Control Strategy for Shunt Active Filter
YANG Xinhu,XIE Xingfeng,MA Jianli,DING Haichang and PEI Xiping.A High-reliability Control Strategy for Shunt Active Filter[J].Automation of Electric Power Systems,2015,39(5):128-133.
Authors:YANG Xinhu  XIE Xingfeng  MA Jianli  DING Haichang and PEI Xiping
Affiliation:College of Electrical and Information Engineering, Lanzhou University of Technology, Lanzhou 730050, China,College of Electrical and Information Engineering, Lanzhou University of Technology, Lanzhou 730050, China,Beijing Chunshu Rectifier Co. Ltd., Beijing 100040, China,Beijing Chunshu Rectifier Co. Ltd., Beijing 100040, China and College of Electrical and Information Engineering, Lanzhou University of Technology, Lanzhou 730050, China
Abstract:To improve the reliability of the active power filter (APF) in face of the DC voltage fluctuation too large to properly compensate for harmonics during load current fluctuation and load sudden stop, a selective harmonic direct detection method based on multiple synchronous rotating coordinates is proposed. And the DC-side voltage control effects are analyzed and compared for d-q harmonic currents detection method or the direct detection method used. A control strategy combining the direct detection method with composite repetitive control is proposed. This strategy not only has direct harmonic detection to ensure system reliability, but also combines the composite repetitive control to ensure dynamic performance and steady-state precision of the system, plus its ability to complete selective harmonic compensation that is flexible. Both simulation and experimental results verify the effectiveness of the research contents.
Keywords:shunt active power filter  high reliability  composite repetitive control  direct detection of harmonics  selective harmonic compensation
本文献已被 CNKI 万方数据 等数据库收录!
点击此处可从《电力系统自动化》浏览原始摘要信息
点击此处可从《电力系统自动化》下载全文