首页 | 本学科首页   官方微博 | 高级检索  
     

改进带电更换500 kV线路耐张绝缘子串的方法
引用本文:张小济.改进带电更换500 kV线路耐张绝缘子串的方法[J].湖北电力,2004,28(1):17-18.
作者姓名:张小济
作者单位:湖北省超高压输变电局,湖北武汉,430064
摘    要:针对500kV输电线路带电更换耐张绝缘子串中存在着绝缘子短接片数过多的问题,提出了用绝缘吊带代替绝缘拉杆的新思路,并将导线侧卡具安装的位置作了适当的调整,使绝缘子串短接的片数得以减少,达到了带电作业的安全规定,具有较高的推广价值。

关 键 词:500  kV输电线路  绝缘子短接  双联碗头  二联板
文章编号:1006-3986(2004)01-0017-02
修稿时间:2003年10月24

To Improve the Method of Live Replacement of 500 kV Tension Insulator String
ZHANG Xiao-ji.To Improve the Method of Live Replacement of 500 kV Tension Insulator String[J].Hubei Electric Power,2004,28(1):17-18.
Authors:ZHANG Xiao-ji
Abstract:In view of the problem that too many pieces had to be shorted during the live replacement of 500 kV tension insulator string.It was pointed out that the irrational design of the working tool was the main cause.By means of proper adjustment of the fix location of clamping device at conductor side,the number of pieces to be shorted was reduced and the safety requirement for live working was met.A new idea of using insulating strip instead of insulating stick was put forward as well.
Keywords:500 kV transmission line  insulator shorted  twin sockets  two-gang board
本文献已被 CNKI 维普 万方数据 等数据库收录!
设为首页 | 免责声明 | 关于勤云 | 加入收藏

Copyright©北京勤云科技发展有限公司  京ICP备09084417号