首页 | 本学科首页   官方微博 | 高级检索  
     


Effects of air temperature and humidity on particle deposition
Authors:Yunlong Han  Yongmei Hu  Fuping Qian
Affiliation:School of Civil Engineering and Architecture, Anhui University of Technology, No. 59, Hudong Road, Ma’anshan, Anhui 243002, PR China
Abstract:Particle deposition in a fully developed turbulent duct flow was studied. The random walk model of Lagrangian approach was used to predict the trajectories of 3000 particles with a density of 900 kg/m3. The effects of thermophoretic force and air humidity were also considered. The results were compared with the previous studies with a particle size range of 0.01–50 μm and air flow velocity of 5 m/s. The profile of dimensionless deposition velocity with relaxation time presents a V-shaped curve and the results are in good agreement with the previous studies.The effects of air temperature and humidity on particle deposition with a particle size of 1 μm were also investigated. The results show that thermophoretic force accelerates particle deposition onto the duct walls with increasing temperature difference between air flow and the duct wall surface. Meanwhile, it was found that particle deposition velocity increases with air humidity.
Keywords:Indoor air quality (IAQ)  Particle deposition  Thermophoretic force  Lagrangian approach
本文献已被 ScienceDirect 等数据库收录!
设为首页 | 免责声明 | 关于勤云 | 加入收藏

Copyright©北京勤云科技发展有限公司  京ICP备09084417号