首页 | 本学科首页   官方微博 | 高级检索  
     

基于膜全热回收的制冷除湿机的实验研究
引用本文:梁才航,张立志.基于膜全热回收的制冷除湿机的实验研究[J].化工学报,2012,0(Z2):151-155.
作者姓名:梁才航  张立志
作者单位:1. 桂林电子科技大学建筑与交通工程学院, 广西 桂林 541004; 2. 华南理工大学化学与化工学院传热强化与过程节能教育部重点实验室, 广东 广州 510640
基金项目:国家自然科学基金项目(51106032);广西科技开发项目(1114020-9);广西自然科学基金项目(2012GXNSFAA053197)~~
摘    要:基于膜全热回收制冷除湿系统是新风独立系统中的一种高效的除湿系统。该系统由高效透湿膜换热器和制冷除湿系统组成。新风和排风在膜全热换热器中进行热质交换。膜换热器回收排风中的全热,同时降低了新风的温度和含湿量。换热之后新风通过蒸发器进行进一步除湿冷却,然后输送到室内。在本研究中,在焓差实验室对基于膜全热回收的制冷除湿样机进行了变工况下的性能实验。研究了在室内温度27℃,湿球温度19℃的条件下,室外空气温度、相对湿度以及空气流量对该系统的除湿能力和COP的影响。实验结果表明膜全热回收制冷除湿系统在高温高湿条件下具有较高的除湿能力和COP。

关 键 词:膜全热换热器  制冷除湿  湿度独立系统  
收稿时间:2012-09-26
修稿时间:2012-10-08

Refrigeration dehumidification system with membrane-based total heat recovery
LIANG Caihang,ZHANG Lizhi.Refrigeration dehumidification system with membrane-based total heat recovery[J].Journal of Chemical Industry and Engineering(China),2012,0(Z2):151-155.
Authors:LIANG Caihang  ZHANG Lizhi
Affiliation:1. School of Architecture and Transportation Engineering, Guilin University of Electronic Technology, Guilin 541004, Guangxi, China; 2. Key Laboratory of Enhanced Heat Transfer and Energy Conservation, Ministry of Education, School of Chemistry and Chemical Engineering, South China University of Technology, Guangzhou 510640, Guangdong, China
Abstract:An independent air dehumidification system is helpful for improving the indoor air quality.Refrigeration dehumidification system with membrane-based total heat recover is the key equipment to realize this goal.The system comprises of two subsystems:membrane total heat recover and refrigeration dehumidifier.The total heat exchanger has a membrane core where the incoming fresh air exchanges moisture and temperature simultaneously with the exhaust air.In this manner,the total heat or enthalpy from the exhaust air is recovered.Then the fresh air flows through a cooling coil where it is dehumidified below the dew point.Finally,the code and dry air are supplied to indoor.A prototype is built in laboratory.Experiments are conducted under variable operating conditions in the enthalpy laboratory.The effects of air flow rates,temperature,and air relative humidity on the air dehumidification rates,cooling capacities,electric power of compressor and COP are investigated under indoor temperature 27℃ and bulk wet-bulb temperature 19℃.The experimental results show that the prototype has a high air dehumidification rates and COP under hot and humid environment.
Keywords:membrane-based total heat exchanger  refrigeration dehumidification  independent humid system
本文献已被 CNKI 等数据库收录!
点击此处可从《化工学报》浏览原始摘要信息
点击此处可从《化工学报》下载全文
设为首页 | 免责声明 | 关于勤云 | 加入收藏

Copyright©北京勤云科技发展有限公司  京ICP备09084417号