首页 | 本学科首页   官方微博 | 高级检索  
     

电缆-架空线混合线路故障行波定位及自适应重合闸控制
引用本文:逯怀东,许磊,刘宗杰,邹亮,李想,曾祥君.电缆-架空线混合线路故障行波定位及自适应重合闸控制[J].电力科学与技术学报,2013(4):31-36.
作者姓名:逯怀东  许磊  刘宗杰  邹亮  李想  曾祥君
作者单位:[1]山东电力集团分司济宁供电公司,山东济宁272000 [2]长沙理工大学智能电网运行与控制湖南省重点实验室,湖南长沙410004
基金项目:国家自然科学基金(61233008;51207013);湖南省科技重大专项(2012FJl003);湖南省高校产业化培育项目(12CY007)
摘    要:提出一种基于预值查表故障搜索算法的混合线路双端行波故障定位方法.基于各个电缆一架空线连接点产生的行波到达线路两端的时间差建立故障区段预置表,利用故障时初始行波波头到达线路两端的时间差查表搜索故障区段,根据故障区段进行重合闸控制,如果故障在电缆上则闭锁重合闸,反之,则开放重合闸;并根据双端行波定位公式计算出故障点位置.EMTP仿真结果表明,提出的行波定位方法可准确定位故障点位置,误差小于50m,且不受故障点位置、故障类型及过渡电阻的影响,可精确实现重合闸,具有较强的实用性.

关 键 词:混合线路  故障定位  预值查表  行波

New method of traveling wave fault location and adaptive reclosing for cable-overhead mixed lines
LU Huai-dong,XU Lei,LIU Zong-jie,ZOU Liang,LI Xiang,ZENG Xiang-jun.New method of traveling wave fault location and adaptive reclosing for cable-overhead mixed lines[J].JOurnal of Electric Power Science And Technology,2013(4):31-36.
Authors:LU Huai-dong  XU Lei  LIU Zong-jie  ZOU Liang  LI Xiang  ZENG Xiang-jun
Affiliation:1. Jining Power Supply Corporation, Shandong Electricity Group Corporation, Jining 272100, China; 2. Hunan Province Key Laboratory of Smart Grids Operation and Control,Changsha University of Science and Technology, Changsha 410004,China)
Abstract:Double-end traveling wave based fault location scheme with preset value lookup table searching is proposed for mixed lines in this paper. Traveling wave transmission time differences from the node of each cable and overhead line to the line double-end are applied to set' the table. When fault occurs, the time difference of faults point generated traveling wave arriving at both ends of the line is compared with the table, and the faulted section is located. If the fault happens on the cable, the reclosing will be prohibited, on the contrary, the reclosing will be permitted. The fault is also located by the double-end traveling wave location formula computing. The EMTP simulation results show that the fault point is located accurately by the proposed location scheme, the error is less than 50m. This technique is practical and not affected by the fault point location, fault type and fault resistance, and the reclosing can be realized exactly.
Keywords:mixed lines  fault location  preset value lookup table  reclosing
本文献已被 维普 等数据库收录!
设为首页 | 免责声明 | 关于勤云 | 加入收藏

Copyright©北京勤云科技发展有限公司  京ICP备09084417号