一种冷凝热分级利用复合型溶液除湿空调系统性能分析
引用本文:张凡,吴薇,张甜湉,苏鹏飞,王红,陈健,李娜,魏丽申.一种冷凝热分级利用复合型溶液除湿空调系统性能分析[J].南京师范大学学报,2014(3):33-42.
作者姓名:张凡  吴薇  张甜湉  苏鹏飞  王红  陈健  李娜  魏丽申
作者单位:1. 南京师范大学能源与机械工程学院,江苏 南京,210042
2. 南京师范大学能源与机械工程学院,江苏 南京210042; 南京师范大学江苏省能源系统过程转化与减排技术工程实验室,江苏 南京210042
摘    要:基于蒸汽压缩式制冷系统冷凝热和太阳能作为溶液再生过程热源的利用,构建了一种新型高效的冷凝热分段利用复合型溶液除湿空调系统,并采用ε-NTU模型对系统进行了理论分析.研究了室内显热负荷比、室外空气状态及新风比对系统性能的影响,并与未利用冷凝热的传统溶液除湿空调系统进行对比,得到系统节能的特性,即使在使用电加热辅助溶液再生时,系统性能仍然优于未利用冷凝热的溶液除湿系统,尤其在ta、RH较小时,系统性能提升更大.

关 键 词:热湿独立处理空调系统  溶液除湿  蒸汽压缩式制冷  ε-NTU模型  性能分析

Performance Analysis of a Hybrid Liquid Desiccant Air-Conditioning System with Sectional Utilization of Condensation Heat
Zhang Fan,Wu Wei,Zhang Tiantian,Su Pengfei,Wang Hong,Chen Jian,Li Na,Wei Lishen.Performance Analysis of a Hybrid Liquid Desiccant Air-Conditioning System with Sectional Utilization of Condensation Heat[J].Journal of Nanjing Nor Univ: Eng and Technol,2014(3):33-42.
Authors:Zhang Fan  Wu Wei  Zhang Tiantian  Su Pengfei  Wang Hong  Chen Jian  Li Na  Wei Lishen
Affiliation:Zhang Fan, Wu Wei, Zhang Tiantian, Su Pengfei, Wang Hong, Chen Jian, Li Na, Wei Lishen (1. School of Energy and Mechanical Engineering, Nanjing Normal University, Nanjing 210042, China) (2. Engineering Laboratory of Energy System Process Conversion and Emission Reduction Technology of Jiangsu Province, Nanjing Normal University, Nanjing 210042, China)
Abstract:In this paper, the condensation heat of vapor compression refrigeration system and solar energy are used as auxiliary heat source in the solution regeneration process. A novel hybrid liquid desiccant air conditioning system is established with efficiently sectional utilization of condensation heat. Theε-NTU model is used to conduct the theoretical analysis of the system. The paper studies the effects of indoor sensible heat load ratio,outdoor air condition as well as fresh air ratio on the performance of the system,and compared the results with the conventional liquid desiccant air con-ditioning system which does not utilize condensation heat as auxiliary heat source. It is concluded that even if electrical energy is used to assist regenerating solution, the system’s performance is better than that of the conventional system without utilization of condensation heat. The promotion will be more especially when ta and RH are relatively little.
Keywords:temperature and humidity independent control air-conditioning system  liquid desiccant  vapor compression refrigeration  ε-NTU  performance analysis