1 000 kV皖南-浙北特高压线路工频参数测试干扰及结果分析
引用本文:马跃,李国满,王少华,崔竹叶,金涌涛,蒋建玲.1 000 kV皖南-浙北特高压线路工频参数测试干扰及结果分析[J].中国电力,2015,48(1):87-91.
作者姓名:马跃  李国满  王少华  崔竹叶  金涌涛  蒋建玲
作者单位:1. 国家电网公司交流建设分公司,北京 100140;
2. 国网浙江省电力公司电力科学研究院,浙江 杭州 310014;
3. 杭州意能电力技术有限公司,浙江 杭州 310014
基金项目:Science and Technology Foundation of SGCC,Science and Technology Foundation of Zhejiang Electric Power Company (5211011306XF).国家电网公司科技资助项目,浙江省电力公司科技资助项目
摘    要:特高压线路工频参数测试干扰分析是选择适合工频参数测试方法及测试结果分析的重要基础。测试了1 000 kV皖南-浙北特高压线路正序和零序参数测试期间的干扰电压信号,分析了其频谱特征;在此基础上,通过与正序参数仿真计算值的对比分析了正序参数实际测试偏差。结果表明:皖南-浙北特高压同塔双回线路工频参数测试期间,干扰电压存在“三相不平衡性及时变性”的特点;工频法和异频法2种不同方法得到的线路参数测试结果存在一定差异;干扰电压“时变”时,线路工频参数测试宜采用异频法。

关 键 词:皖电东送  特高压  同塔双回  工频参数  测试干扰  结果分析  
收稿时间:2014-11-08

Interference Analysis of Power Frequency Parameter Measurement for 1 000 kV Wanan-Zhebei UHV Transmission Line
MA Yue,LI Guoman,WANG Shaohua,CUI Zhuye,JIN Yongtao,JIANG Jianling.Interference Analysis of Power Frequency Parameter Measurement for 1 000 kV Wanan-Zhebei UHV Transmission Line[J].Electric Power,2015,48(1):87-91.
Authors:MA Yue  LI Guoman  WANG Shaohua  CUI Zhuye  JIN Yongtao  JIANG Jianling
Affiliation:1. AC Project Construction Branch, State Grid Corporation of China, Beijing 100140, China;
2. State Grid Zhejiang Electric Power Research Institute, Hangzhou 310014, China;
3. Hangzhou Yineng Power Technology Co., Ltd., Hangzhou 310014, China
Abstract:Interference analysis of power frequency parameter measurement of UHV transmission line is an important basis for selecting appropriate anti-interference test method and analyzing the testing result. The interference voltage signals of 1 000 kV Wannan-Zhebei UHV transmission line were tested during measuring the positive sequence and zero sequence parameters, and their spectrum characteristics was analyzed. On this basis, the field testing error of positive sequence parameters was also analyzed. The results show that the interference voltage has unbalance and time-variant features. Some difference exists between the power frequency parameter testing result obtained by power frequency method and that by variable frequency method. When the interference voltage is time-varied, the variable frequency method should be adopted to measure the power frequency parameter of transmission line.
Keywords:power  transmission  from  Anhui  to  the  eastern  China  region  ultra  high  voltage  (UHV)  double-circuit  line  on  same  tower  power  frequency  parameter  test  interference  result  analysis