首页 | 本学科首页   官方微博 | 高级检索  
     

SF6电流互感器绝缘缺陷的放电及气体分解特性
引用本文:王圆圆,邵颖彪,王世谦,苗福丰,田春筝,汲胜昌.SF6电流互感器绝缘缺陷的放电及气体分解特性[J].中国电力,2016,49(11):63-69.
作者姓名:王圆圆  邵颖彪  王世谦  苗福丰  田春筝  汲胜昌
作者单位:1. 国网河南省电力公司经济技术研究院,河南 郑州 450052;
2. 国网河南省电力公司电力科学研究院,河南 郑州 450052;
3. 西安交通大学 电力设备电气绝缘国家重点实验室,陕西 西安 710049
摘    要:选取铝筒均压型和电容屏均压型的500 kV SF6电流互感器(CT)试品,研究了绝缘子沿面缺陷和复合缺陷下的放电及气体分解特性,并分析了缺陷类型、放电路径长度和采气位置对该特性的影响。发现相位分辨率的脉冲序列(PRPD)谱图是气体分解特性研究的良好辅助手段,改良设计的采气口检测结果更准确。绝缘介质缺陷的典型特征是含C物质(CF4、CS2)的生成。绝缘子沿面缺陷下SO2含量高于SO2F2,S2OF10的含量增长率较低,且放电路径长度会影响典型产物的种类。复合缺陷下SO2F2和SO2的含量增长率较高,S2OF10的含量增长率相对低。

关 键 词:SF6  CT  绝缘缺陷  气体分解  PRPD  
收稿时间:2016-09-08

Discharge and Gas Decomposition of Typical Insulation Defects in 500 kV SF6 Current Transformer
WANG Yuanyuan,SHAO Yingbiao,WANG Shiqian,MIAO Fufeng,TIAN Chunzheng,JI Shengchang.Discharge and Gas Decomposition of Typical Insulation Defects in 500 kV SF6 Current Transformer[J].Electric Power,2016,49(11):63-69.
Authors:WANG Yuanyuan  SHAO Yingbiao  WANG Shiqian  MIAO Fufeng  TIAN Chunzheng  JI Shengchang
Affiliation:1. State Grid Henan Economic Research Institute, Zhengzhou 450052, China;
2. State Grid Henan Electric Power Research Institute, Zhengzhou 450052, China;
3. State Key Laboratory of Electrical Insulation and Power Equipment, Xi’an Jiaotong University, Xi’an 710049, China;
Abstract:Two 500 kV SF6 CTs with aluminum cylinder grading structure and cone capacitor grading structure are selected to analyze discharge and gas decomposition characteristics of insulator surface defect and combining defect. The influences of defect type, discharge path length and sampling positions are discussed. It is found that measuring PRPD is an effective assistant method for gas analysis. The detection results of the improved sample port are more accurate than that of regular one. Typical gas decomposition products of the insulation material related defects are CF4 and CS2. In insulator surface defect, concentration of SO2 is higher than SO2F2; the growth rate of S2OF10 concentration is relatively low; types of decomposition products vary with discharge path length. In the combining defect, the growth rates of SO2F2 and SO2 are relatively higher than that of S2OF10.
Keywords:SF6  CT  insulation defect  gas decomposition  PRPD  
本文献已被 CNKI 等数据库收录!
点击此处可从《中国电力》浏览原始摘要信息
点击此处可从《中国电力》下载全文
设为首页 | 免责声明 | 关于勤云 | 加入收藏

Copyright©北京勤云科技发展有限公司  京ICP备09084417号