首页 | 本学科首页   官方微博 | 高级检索  
     

海上风电场故障特性及保护配合的研究
引用本文:卢智雪,刘天琪,丁媛媛.海上风电场故障特性及保护配合的研究[J].电力系统保护与控制,2018,46(10):144-151.
作者姓名:卢智雪  刘天琪  丁媛媛
作者单位:四川大学电气信息学院
摘    要:一般海上风电场所选用设备和线路与陆上风电场有所不同,有必要对海上风电场的继电保护配置进行专门研究。利用ETAP仿真软件对风电场内元件及送出线故障时各元件的短路电流和机端电压跌落情况进行分析,并研究海上风电场本身特征和故障特性。在多个风电场并网时,风机会提供不容忽视的短路电流,短路点成为双侧电源供电。为此,考虑其特性及风机低电压穿越能力,提出海上风电场各元件和线路的保护配置方案及其整定原则。并对ETAP软件上搭建的某海上风电场模型进行保护及动作时序配合的仿真,验证了所提保护配置方案及动作时序的正确性和合理性。

关 键 词:海上风电场  故障特性  继电保护  配合方案  整定原则
收稿时间:2017/5/6 0:00:00
修稿时间:2017/8/3 0:00:00

Study on fault characteristics and protection cooperation of the offshore wind farm
LU Zhixue,LIU Tianqi and DING Yuanyuan.Study on fault characteristics and protection cooperation of the offshore wind farm[J].Power System Protection and Control,2018,46(10):144-151.
Authors:LU Zhixue  LIU Tianqi and DING Yuanyuan
Affiliation:School of Electrical Information, Sichuan University, Chengdu 610065, China,School of Electrical Information, Sichuan University, Chengdu 610065, China and School of Electrical Information, Sichuan University, Chengdu 610065, China
Abstract:In general, the equipment and lines used in offshore wind farms are different from those of onshore wind farms. Therefore, it is necessary to study the configuration of relay protection for offshore wind farms. This paper analyzes the short circuit current and terminal voltage drop with the fault of the components in the wind power field and the outgoing line by the simulation software of ETAP, and studies the characteristics and fault characteristics of the offshore wind farm. When multiple wind farms are connected to the grid, the wind turbines will provide short-circuit current that cannot be ignored and it will be a bilateral power supply for the short-circuit point. Therefore, considering the characteristics and the low-voltage ride-through capability of the wind turbine, it proposes the protection scheme and the setting principle of the components and lines of the offshore wind farm. The cooperation of the protection program and action sequence of the offshore wind farm model built on the software ETAP is simulated, and the correctness and rationality of the proposed protection scheme and action sequence are verified.
Keywords:offshore wind farm  fault characteristics  relay protection  cooperation program  setting principle
本文献已被 CNKI 等数据库收录!
点击此处可从《电力系统保护与控制》浏览原始摘要信息
点击此处可从《电力系统保护与控制》下载全文
设为首页 | 免责声明 | 关于勤云 | 加入收藏