首页 | 本学科首页   官方微博 | 高级检索  
     

同塔双回直流输电系统过电压特性研究
引用本文:廖志超,贺恒鑫,韩云,张佳鑫.同塔双回直流输电系统过电压特性研究[J].高压电器,2013(5):60-68,73.
作者姓名:廖志超  贺恒鑫  韩云  张佳鑫
作者单位:西安高压电器研究院有限责任公司;华中科技大学
摘    要:对于同塔双回直流输电系统,考虑到其线路之间的电磁耦合,一极发生故障将同时在健全极线感应出过电压,对正常运行极的换流站设备和线路造成影响,因此笔者认为对同塔双回直流输电系统换流站的过电压特性的研究是同塔双回直流输电工程设计的核心技术环节。为了进行具体的研究分析,笔者以溪洛渡±500 kV同塔双回直流输电工程为例,结合此工程主回路设计方案,利用PSCAD/EMTDC电磁暂态仿真软件,对±500 kV同塔双回直流输电工程的各种过电压特性进行系统研究。通过系统模拟仿真,综合分析避雷器限压作用的影响,这些研究对于防范类似故障的发生以及处理等具有一定的借鉴意义。

关 键 词:同塔双回  高压直流输电  避雷器  过电压

Research on Overvoltage Protection for ±500 kV Double-circuit HVDC Transmission System
LIAO Zhi-chao,HE Heng-xin,HAN Yun,ZHANG Jia-xin.Research on Overvoltage Protection for ±500 kV Double-circuit HVDC Transmission System[J].High Voltage Apparatus,2013(5):60-68,73.
Authors:LIAO Zhi-chao  HE Heng-xin  HAN Yun  ZHANG Jia-xin
Affiliation:1.Xi’an High Voltage Apparatus Research Institute Co.,Ltd.,Xi’an 710077,China; 2.Huazhong University of Science and Technology,Wuhan 430074,China)
Abstract:For the double-circuit transmission line,there exist electrostatic coupling and electromagnetic coupling between the two lines.Once one-circuit fault,it will affects the other single-circuit normal operation.Therefore,the authors think that the studies on the over-voltage characteristics of double-circuit transmission line are the core technology of the double-circuit DC transmission engineering design.In this paper,to conduct specific research and analysis,take Xiluodu-Guangdong double-circuit transmission line as an example,binging the main circuit system design scheme,all kinds of over-voltage characteristics for ±500 kV double-circuit HVDC transmission system are studied by using PSCAD/EMTDC.Through the system simulation and comprehensive analysis of the surge arresters used,it is of a certain significance for preventing and dealing with similar faults.
Keywords:double-circuit  HVDC transmission system  arrester  over-voltage
本文献已被 CNKI 等数据库收录!
设为首页 | 免责声明 | 关于勤云 | 加入收藏

Copyright©北京勤云科技发展有限公司  京ICP备09084417号