首页 | 本学科首页   官方微博 | 高级检索  
     

换流阀三角形侧零序环流对阀短路保护的影响
引用本文:田庆,王晓希.换流阀三角形侧零序环流对阀短路保护的影响[J].高压电器,2008,44(6).
作者姓名:田庆  王晓希
作者单位:国网运行有限公司宜昌超高压管理处,湖北,宜昌,443005
摘    要:笔者研究了换流阀三角形侧零序环流对阀短路保护误动作的影响。通过分析葛洲坝换流站两次阀短路保护无动作的情况,根据双极阀短路保护判据,指出零序环流使CT暂态饱和是这两次事故的主要原因,同时相应地给出了解决办法,为将来高压直流更好的安全稳定运行提供参考。

关 键 词:高压直流  阀短路保护  零序环流  误动作

Influence of Converter Transformer D-bridge Zero Sequence Circulating Current on Valve Short Circuit Protection
TIAN Qing,WANG Xiao-xi.Influence of Converter Transformer D-bridge Zero Sequence Circulating Current on Valve Short Circuit Protection[J].High Voltage Apparatus,2008,44(6).
Authors:TIAN Qing  WANG Xiao-xi
Abstract:This paper studies the influence of converter transformer D-bridge zero sequence circulating current on valve short circuit protection.A case study indicates the fault trips of D-bridge differential protection due to CT transient saturation in Gezhouba converter station leads to breakdown of equipments for two times,according to the criterion of valve short circuit protection.Corresponding methods are presented for solving this problem.
Keywords:HVDC  valve short circuit protection  zero sequence circulating current  fault trip
本文献已被 维普 万方数据 等数据库收录!
设为首页 | 免责声明 | 关于勤云 | 加入收藏

Copyright©北京勤云科技发展有限公司  京ICP备09084417号