首页 | 本学科首页   官方微博 | 高级检索  
     


Development of Compact 500 kV 8000 a Gas Insulated Transmission Line-Dust Control during Field Jointing and Method for Detecting Conductive Particles
Authors:Kaminaga  K Koshiishi  M Hayashi  T Matsuki  M Hara  T Sugiyama  N
Affiliation:The Tokyo Electric Power Co., Inc. Tokyo, Japan;
Abstract:This paper describes the results of studies made on dust control during field jointing and a method for detecting conductive particles after installation in the development of a compact 500 kV 8000 A gas insulated transmission line (GIL). The study on dust control during field jointing proved that field jointing of the compact GIL can be done like conventional GIL in an easily fabricated vinyl shelter without a clean air flow. Harmful conductive particles can be detected with an Acoustic Emission (AE) sensor. This sensor is effective in improving the reliability of the compact GIL when used with a suitable ac voltage during field test. A 120 m long test line of compact 500 kV 8000 A GIL was constructed and, in a long-term field test, proved to have properties sufficient for practical use.
Keywords:
设为首页 | 免责声明 | 关于勤云 | 加入收藏

Copyright©北京勤云科技发展有限公司  京ICP备09084417号