风电T接双电源系统对距离保护的影响分析
引用本文:陈伟伟,李凤婷,张玉,樊艳芳.风电T接双电源系统对距离保护的影响分析[J].继电器,2015,43(7):108-114.
作者姓名:陈伟伟  李凤婷  张玉  樊艳芳
作者单位:新疆大学可再生能源发电与并网技术教育部工程研究中心,新疆 乌鲁木齐 830047;新疆大学可再生能源发电与并网技术教育部工程研究中心,新疆 乌鲁木齐 830047;新疆大学可再生能源发电与并网技术教育部工程研究中心,新疆 乌鲁木齐 830047; 国家电网新疆送变电工程公司,新疆 乌鲁木齐 830047;新疆大学可再生能源发电与并网技术教育部工程研究中心,新疆 乌鲁木齐 830047
基金项目:国家自然科学基金项目(51267019);新疆维吾尔自治区自然科学基金资助项目(2012211A002);新疆维吾尔自治区高校科研重点项目(XJEDU2011I05)
摘    要:风电并网影响接入系统距离保护测量阻抗及保护动作特性,风电T型接入对保护的影响有其特殊性。推导风电T接双电源系统距离保护测量阻抗公式,研究故障点位置、风电场运行方式及过渡电阻对风电T接线路距离保护测量阻抗的影响,并讨论上述因素对本段距离保护和下段距离保护的影响。以新疆某地区风电T接系统为算例,仿真验证了理论分析的正确性。研究成果可为风电T接电网的继电保护配置和整定提供依据,具有一定的实际应用价值和意义。

关 键 词:风电T接  距离保护  影响因素  保护动作特性
收稿时间:2014/6/20 0:00:00
修稿时间:9/2/2014 12:00:00 AM

Impact of wind farm on distance protection for T-connected to the dual power system
CHEN Weiwei,LI Fengting,ZHANG Yu and FAN Yanfang.Impact of wind farm on distance protection for T-connected to the dual power system[J].Relay,2015,43(7):108-114.
Authors:CHEN Weiwei  LI Fengting  ZHANG Yu and FAN Yanfang
Affiliation:Engineering Research Center of Education Ministry for Renewable Energy Power Generation and Grid Technology, Xinjiang University, Urumqi 830047, China;Engineering Research Center of Education Ministry for Renewable Energy Power Generation and Grid Technology, Xinjiang University, Urumqi 830047, China;Engineering Research Center of Education Ministry for Renewable Energy Power Generation and Grid Technology, Xinjiang University, Urumqi 830047, China; Xinjiang Power Transmission and Substation Engineering Company, Urumqi 830047, China;Engineering Research Center of Education Ministry for Renewable Energy Power Generation and Grid Technology, Xinjiang University, Urumqi 830047, China
Abstract:Wind power integration on power system influences the measured impedance as well as operation characteristics of distance protection. The impacts has particularity for wind farm connecting to the grid with T-type. The distance protection measure impedance formula is deduced for wind farm connected to dual power system with T-type. The impacts of fault location, operation mode of wind farm and transition resistance on measured impedance are studied, and the influence of these factors on the distance protection and next distance protection are discussed. Taking a wind farm connected to the grid with T-type in Xinjiang as an example, the simulation model is established, the correctness of theoretical analysis are verified by simulation. The study provides a theoretical basis for relay setting and configuration, and has theoretical significance and practical value.
Keywords:wind power T-type connection  distance protection  influencing factors  protection operation characteristics