线路区外故障引起母差保护误动作分析及对策
引用本文:黄涛.线路区外故障引起母差保护误动作分析及对策[J].江苏电机工程,2009,28(4):16-18.
作者姓名:黄涛
作者单位:镇江供电公司,江苏,镇江,212001
摘    要:分析了某220kV变电站由于某110kV线路重合于永久性故障,引起110kV母差保护误动的情况,即当该线路重合于C相永久性故障时,从该线路间隔观察到A相有一个毛刺电流,从而导致110kV母差保护A相动作。从理论上分析阐述了该事件发生的可能原因,并通过试验加以验证,针对这种情况提出相应的对策避免此类事件再次发生。

关 键 词:线路故障  母差保护  TA饱和  误动作

Analysis and Measures of Misoperation of Bus Differential Protection Caused By Outside Faults
HUANG Tao.Analysis and Measures of Misoperation of Bus Differential Protection Caused By Outside Faults[J].Jiangsu Electrical Engineering,2009,28(4):16-18.
Authors:HUANG Tao
Affiliation:Zhengjiang power supply company;Zhengjiang 212001;China
Abstract:A 110 kV bus differential protection misoperation is analyzed when a permanent fault is reclosed to the system in a 220 kV substation.When C-phase permanent fault is reclosed,a burr current appears in A-phase which causes the action of A-phase bus differential protection.The reason of misoperation is presented based on theoretical analysis,and is verified through test.Some measures are proposed to avoid the recurrence of similar accidents.
Keywords:line fault  bus differential protection  TA saturation  misoperation  