异步联网方式下云南电网超低频振荡的抑制措施与试验
引用本文:张建新,刘春晓,陈亦平,张勇,黄河,付超,李鹏.异步联网方式下云南电网超低频振荡的抑制措施与试验[J].南方电网技术,2016,10(7):35-39.
作者姓名:张建新  刘春晓  陈亦平  张勇  黄河  付超  李鹏
作者单位:中国南方电网电力调度控制中心,广州510623,中国南方电网电力调度控制中心,广州510623,中国南方电网电力调度控制中心,广州510623,中国南方电网电力调度控制中心,广州510623,中国南方电网电力调度控制中心,广州510623,南方电网科学研究院,广州510080,南方电网科学研究院,广州510080
摘    要:在云南异步联网验证性试验过程中,云南电网频率出现了长时间的超低频率振荡现象,威胁电网的安全稳定运行。在单机系统及BPA仿真系统下分析了水电机组调速器不同参数以及直流频率限制控制器对频率稳定性的影响,通过仿真计算提出了调整云南水电机组调速器死区、优化PI参数等措施,并比较了不同措施的特点。经过实际电网大、小扰动试验验证,本文所提措施可以有效解决异步后云南电网的超低频振荡问题。

关 键 词:异步联网  超低频振荡  抑制措施  水轮机调速器  一次调频  试验验证

Countermeasures and Experiments on Ultra Low Frequency Oscillation of Yunnan Power Grid in Asynchronous Interconnection Mode
ZHANG Jianxin,LIU Chunxiao,CHEN Yiping,ZHANG Yong,HUANG He,FU Chao and LI Peng.Countermeasures and Experiments on Ultra Low Frequency Oscillation of Yunnan Power Grid in Asynchronous Interconnection Mode[J].Southern Power System Technology,2016,10(7):35-39.
Authors:ZHANG Jianxin  LIU Chunxiao  CHEN Yiping  ZHANG Yong  HUANG He  FU Chao and LI Peng
Affiliation:CSG Power Dispatching Control Center, Guangzhou 510623, China,CSG Power Dispatching Control Center, Guangzhou 510623, China,CSG Power Dispatching Control Center, Guangzhou 510623, China,CSG Power Dispatching Control Center, Guangzhou 510623, China,CSG Power Dispatching Control Center, Guangzhou 510623, China,Electrical Power Research Institute, CSG,Guangzhou 510080, China and Electrical Power Research Institute, CSG,Guangzhou 510080, China
Abstract:During the practical asynchronous interconnection experiment, Yunnan Power Grid experienced an ultra low frequency oscillation for a long period, which threatened the security and stability of China Southern Power Grid(CSG). In this paper, the effects of different hydro governor parameters and HVDC frequency limitation control (FLC) on the frequency stability are analyzed in a single generator system and the BPA simulation system. From a large amount of simulation, the measures of optimally adjusting the dead zones and PI parameters of hydro governors are proposed, and the characteristics of different measures are compared. The proposed measures can effectively solve the ultra low frequency oscillation problem in asynchronous interconnection mode of Yunnan Power Grid, which has been verified by the large and small disturbance experiments on the actual power grid.
Keywords:asynchronous interconnection  ultra low frequency oscillation  countermeasures  hydro governors  primary frequency control  experimental verification
本文献已被 CNKI 等数据库收录!
点击此处可从《南方电网技术》浏览原始摘要信息
点击此处可从《南方电网技术》下载全文