首页 | 本学科首页   官方微博 | 高级检索  
     

考虑容量及电压约束的配电网可靠性评估前推故障扩散法
引用本文:昝贵龙,赵华,吴延琳,黄宗君,王主丁.考虑容量及电压约束的配电网可靠性评估前推故障扩散法[J].电力系统自动化,2017,41(7):61-67.
作者姓名:昝贵龙  赵华  吴延琳  黄宗君  王主丁
作者单位:输配电装备及系统安全与新技术国家重点实验室(重庆大学), 重庆市 400044,国网重庆綦南供电公司, 重庆市 401420,国网陕西省电力公司经济技术研究院, 陕西省西安市 710000,国网陕西省电力公司经济技术研究院, 陕西省西安市 710000,输配电装备及系统安全与新技术国家重点实验室(重庆大学), 重庆市 400044
摘    要:基于元件优化编号,利用前推故障扩散法仅需数次网络遍历便可确定元件停运的影响范围和隔离范围,枚举故障元件时无需再次遍历网络即可对节点进行分类并累加得到其可靠性指标,证明了算法的时间复杂度为O(N)。根据各元件停运负荷转供路径潮流变化,近似计算相应的容量允许负荷转供率和电压允许负荷转供率,基于节点分支线最大电压降进行快速电压约束校验,提出了考虑设备载流量和节点电压约束的可靠性计算简化模型,无需多次调用完整潮流计算程序。对典型配电网的计算分析表明了所提出的模型算法的有效性和实用性。

关 键 词:配电网  可靠性评估  前推故障扩散法  节点分类  容量约束  电压约束  网络元件遍历
收稿时间:2016/6/14 0:00:00
修稿时间:2017/1/9 0:00:00

Forward Failure Diffusion Algorithm for Reliability Evaluation of Distribution Networks Considering Capacity and Voltage Constraints
ZAN Guilong,ZHAO Hu,WU Yanlin,HUANG Zongjun and WANG Zhuding.Forward Failure Diffusion Algorithm for Reliability Evaluation of Distribution Networks Considering Capacity and Voltage Constraints[J].Automation of Electric Power Systems,2017,41(7):61-67.
Authors:ZAN Guilong  ZHAO Hu  WU Yanlin  HUANG Zongjun and WANG Zhuding
Affiliation:State Key Laboratory of Power Transmission Equipment & System Security and New Technology(Chongqing University), Chongqing 400044, China,State Grid Chongqing Qinan Power Supply Company, Chongqing 401420, China,Economic and Technological Research Institute of State Grid Shaanxi Electric Power Company, Xi''an 710000, China,Economic and Technological Research Institute of State Grid Shaanxi Electric Power Company, Xi''an 710000, China and State Key Laboratory of Power Transmission Equipment & System Security and New Technology(Chongqing University), Chongqing 400044, China
Abstract:Based on the optimal ordering of network elements, the power outage range and isolation range are determined by the forward failure diffusion algorithm including several times of global network ergodic search. The nodes can be classified by enumerating fault elements without more global network search and accumulated to obtain the reliability indices, proving that the time complexity of the algorithm is O(N). According to the current changes through the load transfer path of corresponding outage element, the load transfer rates constrained by capacity and voltage are approximately calculated. Based on the maximum voltage drop of branches, the voltage constraint is conveniently checked. Thus, a simplified reliability evaluation model considering element capacity and node voltage constraints is proposed, with no need to invoke the full power flow calculation program. The validity and effectiveness of the proposed algorithm is verified through calculation and analysis of typical distribution networks.
Keywords:distribution network  reliability evaluation  forward failure diffusion algorithm  node classification  capacity constraint  voltage constraint  network element traversal
本文献已被 CNKI 等数据库收录!
点击此处可从《电力系统自动化》浏览原始摘要信息
点击此处可从《电力系统自动化》下载全文
设为首页 | 免责声明 | 关于勤云 | 加入收藏

Copyright©北京勤云科技发展有限公司  京ICP备09084417号