基于零序导纳变化的灵活接地系统接地故障方向判别算法
引用本文:杨帆,金鑫,沈煜,雷杨,薛永端,徐丙垠.基于零序导纳变化的灵活接地系统接地故障方向判别算法[J].电力系统自动化,2020,44(17):88-94.
作者姓名:杨帆  金鑫  沈煜  雷杨  薛永端  徐丙垠
作者单位:1.国网湖北省电力有限公司电力科学研究院,湖北省武汉市 430077;2.中国石油大学(华东)新能源学院,山东省青岛市 266580;3.山东科汇电力自动化股份有限公司,山东省淄博市 255087
基金项目:国家自然科学基金资助项目(51477184)。
摘    要:目前灵活接地系统的接地保护大多直接采用小电阻接地系统的定时限零序过电流保护,存在高阻接地时保护灵敏度不足以及故障信息利用不充分等问题。通过分析灵活接地系统发生单相接地故障时,并联小电阻投入前后故障点上、下游及健全线路的零序测量导纳特征,发现并联小电阻投入前后故障点下游及健全线路的零序测量导纳不变,模值比为1,而故障点上游线路零序测量导纳的模值比远大于1,基于此提出了基于零序导纳变化的灵活接地系统接地故障方向判别算法。数字仿真和现场试验数据表明,该方法准确率高,不易受线路参数和过渡电阻等因素影响,可与定时限零序过电流保护配合使用,能满足现场实用要求。

关 键 词:灵活接地方式  单相接地故障  零序导纳  故障方向
收稿时间:2019/12/8 0:00:00
修稿时间:2020/5/4 0:00:00

Dicrimination Algorithm of Grounding Fault Direction Based on Variation of Zero-sequence Admittance in Flexible Grounding System
YANG Fan,JIN Xin,SHEN Yu,LEI Yang,XUE Yongduan,XU Bingyin.Dicrimination Algorithm of Grounding Fault Direction Based on Variation of Zero-sequence Admittance in Flexible Grounding System[J].Automation of Electric Power Systems,2020,44(17):88-94.
Authors:YANG Fan  JIN Xin  SHEN Yu  LEI Yang  XUE Yongduan  XU Bingyin
Affiliation:1.Electric Power Research Institute of State Grid Hubei Electric Power Co., Ltd., Wuhan 430077, China;2.College of New Energy, China University of Petroleum (East China), Qingdao 266580, China;3.Shandong Kehui Power Automation Co., Ltd., Zibo 255087, China
Abstract:At present, grounding fault protection of most flexible grounding system directly adopts the zero-sequence time-limit overcurrent protection of traditional low-resistance grounding system, which has problems including insufficient protection sensitivity and insufficient utilization of fault information when grounding via high-resistance. When single-phase grounding fault occurs in flexible grounding system, the characteristics of zero-sequence admittance measurement of healthy lines, upstream and downstream line of the fault point before and after switch-in of parallel small resistance are analyzed. It is found that the zero-sequence admittance measurement of healthy lines and the downstream line of the fault point remain unchanged, and the modulus ratio of admittance before and after switch-in of parallel resistance is 1, while the ratio of the upstream line of the fault point is much greater than 1. Based on this, a discrimination algorithm of grounding fault direction based on variation of zero-sequence admittance in flexible grounding system is proposed. Digital simulation and field experiment data show that this method has high accuracy, and it will not be easily affected by factors such as line parameters and transition resistance. The proposed method can be used in conjunction with zero-sequence time-limit overcurrent protection, which can meet practical field requirements.
Keywords:flexible grounding mode  single-phase grounding fault  zero-sequence admittance  fault direction