首页 | 本学科首页   官方微博 | 高级检索  
     

适应稳定控制系统动作的备自投开放判据
引用本文:梁鑫钰,张哲,尹项根,陈国炎,杨凡,裴超.适应稳定控制系统动作的备自投开放判据[J].电力系统自动化,2017,41(8):105-109.
作者姓名:梁鑫钰  张哲  尹项根  陈国炎  杨凡  裴超
作者单位:强电磁工程与新技术国家重点实验室(华中科技大学), 湖北省武汉市 430074,强电磁工程与新技术国家重点实验室(华中科技大学), 湖北省武汉市 430074,强电磁工程与新技术国家重点实验室(华中科技大学), 湖北省武汉市 430074,广州供电局有限公司, 广东省广州市 510000,强电磁工程与新技术国家重点实验室(华中科技大学), 湖北省武汉市 430074,强电磁工程与新技术国家重点实验室(华中科技大学), 湖北省武汉市 430074
基金项目:国家高技术研究发展计划(863计划)资助项目(2015AA050201)
摘    要:传统备自投方法难以正确区分进线故障导致母线失压和稳定控制系统动作切除进线导致母线失压两种情况,可能导致备自投误动或拒动,影响电网的稳定运行和供电可靠性。文中根据稳定控制系统动作和进线故障切除时,母线电压和进线电流的不同变化特点,提出了一种适应稳定控制系统动作的备自投开放判据。该判据可在稳定控制系统动作切除进线时,自动闭锁备自投;而当进线故障切除时,可靠开放备自投。仿真测试验证了所提判据的正确性。

关 键 词:备自投  稳定控制系统  短路故障  备自投开放判据
收稿时间:2016/10/14 0:00:00
修稿时间:2017/2/13 0:00:00

Opening Criterion for Automatic Switchover Adapted to Actions of Security and Stability Control System
LIANG Xinyu,ZHANG Zhe,YIN Xianggen,CHEN Guoyan,YANG Fan and PEI Chao.Opening Criterion for Automatic Switchover Adapted to Actions of Security and Stability Control System[J].Automation of Electric Power Systems,2017,41(8):105-109.
Authors:LIANG Xinyu  ZHANG Zhe  YIN Xianggen  CHEN Guoyan  YANG Fan and PEI Chao
Affiliation:State Key Laboratory of Advanced Electromagnetic Engineering and Technology (Huazhong University of Science and Technology), Wuhan 430074, China,State Key Laboratory of Advanced Electromagnetic Engineering and Technology (Huazhong University of Science and Technology), Wuhan 430074, China,State Key Laboratory of Advanced Electromagnetic Engineering and Technology (Huazhong University of Science and Technology), Wuhan 430074, China,Guangzhou Power Supply Bureau, Guangzhou 510000, China,State Key Laboratory of Advanced Electromagnetic Engineering and Technology (Huazhong University of Science and Technology), Wuhan 430074, China and State Key Laboratory of Advanced Electromagnetic Engineering and Technology (Huazhong University of Science and Technology), Wuhan 430074, China
Abstract:Traditional automatic switchover methods can hardly correctly distinguish between two cases: the cause of bus voltage loss is the incoming line fault or the cut of incoming line by the security and stability control system. It may cause the incorrect operation or refusing action of the automatic switchover device, which affects the stable operation of power system and the reliability of power supply. According to different variation characteristics of bus voltage and incoming line current when the security and stability control system cuts the incoming line and the incoming line is removed because of the fault. This paper proposes an opening criterion for automatic switchover to adapt to the actions of the security and stability control system. The criterion can lock the automatic switchover function when the security and stability control system cuts the incoming line, and it can also reliably open the automatic switchover function when the incoming line is removed due to fault. Finally, the correctness of the criterion is verified by a simulation test. This work is supported by National High Technology Research and Development Program of China(863 Program)(No. 2015AA050201).
Keywords:automatic switchover  security and stability control system  short-circuit fault  opening criterion for automatic switchover
本文献已被 CNKI 等数据库收录!
点击此处可从《电力系统自动化》浏览原始摘要信息
点击此处可从《电力系统自动化》下载全文
设为首页 | 免责声明 | 关于勤云 | 加入收藏