首页 | 本学科首页   官方微博 | 高级检索  
     

选相及方向元件在风电接入系统中的适应性分析
引用本文:王晨清,宋国兵,汤海雁,常仲学,李端祯.选相及方向元件在风电接入系统中的适应性分析[J].电力系统自动化,2016,40(1):89-95.
作者姓名:王晨清  宋国兵  汤海雁  常仲学  李端祯
作者单位:西安交通大学电气工程学院, 陕西省西安市 710049,西安交通大学电气工程学院, 陕西省西安市 710049,中国电力科学研究院, 北京市 100192,西安交通大学电气工程学院, 陕西省西安市 710049,西安交通大学电气工程学院, 陕西省西安市 710049
基金项目:国家重点基础研究发展计划(973计划)资助项目(2012CB215105)
摘    要:对传统选相及方向元件在风电接入系统中的适应性进行了研究分析。传统选相和方向元件均基于故障序分量网络分析,故障期间风电系统正负序阻抗相差较大且幅值远大于常规电网的特点使得风电侧正负序电流分支系数具有较大偏差,从而造成了基于正负序电流分支系数近似相等的传统选相和方向元件并不适用于风电接入系统。PSCAD建模仿真和现场故障录波数据验证了适应性分析结论。最后基于适应性分析结论给出了风电接入系统的选相和方向元件建议。

关 键 词:风电系统    故障特征    选相元件    方向元件    保护适应性
收稿时间:6/1/2015 12:00:00 AM
修稿时间:2015/12/2 0:00:00

Adaptability Analysis of Phase Selectors and Directional Relays in Power Systems Integrated with Wind Farms
WANG Chenqing,SONG Guobing,TANG Haiyan,CHANG Zhongxue and LI Duanzhen.Adaptability Analysis of Phase Selectors and Directional Relays in Power Systems Integrated with Wind Farms[J].Automation of Electric Power Systems,2016,40(1):89-95.
Authors:WANG Chenqing  SONG Guobing  TANG Haiyan  CHANG Zhongxue and LI Duanzhen
Abstract:The adaptability of traditional phase selectors and directional relays in power systems integrated with wind farms is studied. Additional fault network is the basis for both traditional phase selectors and directional relays. The positive and negative sequence impedances of the wind power system vary widely and their amplitudes are both much larger than that of a regular power system during a fault. The impedance characteristics will then lead to a big difference between positive and negative current branched coefficients at the wind power side. Thus traditional phase selectors and directional relays based on equal positive and negative current branched coefficients are not necessarily suitable for wind power integration. Data from PSCAD simulation and field fault record have verified the theoretical analysis of adaptability. Eventually, research recommendations for phase selectors and directional relays suitable for power systems integrated with wind farms are given according to the adaptability analysis. This work is supported by National Basic Research Program of China (973 Program) (No. 2012CB215105).
Keywords:wind power system  fault characteristics  phase selector  directional relay  protection adaptation
本文献已被 CNKI 等数据库收录!
点击此处可从《电力系统自动化》浏览原始摘要信息
点击此处可从《电力系统自动化》下载全文
设为首页 | 免责声明 | 关于勤云 | 加入收藏

Copyright©北京勤云科技发展有限公司  京ICP备09084417号