首页 | 本学科首页   官方微博 | 高级检索  
     

带并联电抗器输电线路拍频电流幅值分析
引用本文:钟高跃,宋国兵,王欢欢,杨远航,马志宾.带并联电抗器输电线路拍频电流幅值分析[J].电力系统自动化,2015,39(11):139-145.
作者姓名:钟高跃  宋国兵  王欢欢  杨远航  马志宾
作者单位:西安交通大学电气工程学院,陕西省西安市,710049
基金项目:国家自然科学基金资助项目(50877062)
摘    要:目前在自适应单相重合闸中缺乏对拍频电流表达式、拍频电流是否一定存在及其幅值范围的研究。单相瞬时性故障消失后,拍频电流不存在或过小,都会影响重合闸判定的可靠性。拍频电流受健全相电压和故障消失后线路中元器件初始状态的影响,采用叠加原理得到完整的拍频电流表达式;通过分析表达式得出最小拍频电流及其出现的条件,分析出拍频电流为零属于小概率事件;拍频电流受故障时刻、故障持续时间、电弧电阻、电源相角差及故障位置等共同影响,使得不同工况下的拍频电流差异明显,若幅值过小,将会影响重合闸判定的可靠性。文中利用正交实验的方法给出某500kV输电线路拍频电流幅值大小的范围,证明了在工程实践中可以用拍频电流实现自适应重合闸。

关 键 词:输电线路  并联电抗器  拍频电流  幅值范围  自适应重合闸
收稿时间:3/3/2014 12:00:00 AM
修稿时间:2015/4/28 0:00:00

Analysis of Beat Frequency Current Amplitude of Transmission Lines with Shunt Reactors
ZHONG Gaoyue,SONG Guobing,WANG Huanhuan,YANG Yuanhang and MA Zhibin.Analysis of Beat Frequency Current Amplitude of Transmission Lines with Shunt Reactors[J].Automation of Electric Power Systems,2015,39(11):139-145.
Authors:ZHONG Gaoyue  SONG Guobing  WANG Huanhuan  YANG Yuanhang and MA Zhibin
Abstract:At present, researches on the adaptive reclosure lack an analytic expression for beat frequency current about whether the beat frequency current definitely exists and the range of amplitude of the current in adaptive reclosure. The amplitude may be nonexistent or too small when the single-phase transient fault disappears, which will affect the reliability of reclosing determination. The beat frequency current in the shunt reactor is not only affected by sound phase voltage but also by the initial state of components of transmission line when fault disappears. Based on the superposition principle, the complete expression of beat frequency current is obtained, by an analysis of which the minimum beat frequency current and conditions for its occurrence are obtained. It is concluded that the beat frequency current being zero belongs to small probability event. The current is affected by fault time, arc duration, arc resistance, phase angle difference and fault location that make the amplitude obvious. If the amplitude is too small, it will affect the reliability of the reclosing determination. The paper gives the range of amplitude of the beat frequency current on 500 kV transmission lines using the method of the orthogonal experiment in mathematical statistics, proving the beat frequency current can be applied to engineering. This work is supported by National Natural Science Foundation of China(No. 50877062).
Keywords:transmission line  shunt reactor  beat frequency current  range of amplitude  adaptive reclosure
本文献已被 CNKI 万方数据 等数据库收录!
点击此处可从《电力系统自动化》浏览原始摘要信息
点击此处可从《电力系统自动化》下载全文
设为首页 | 免责声明 | 关于勤云 | 加入收藏

Copyright©北京勤云科技发展有限公司  京ICP备09084417号