快速识别转换性故障的变压器差动保护新判据
引用本文:杨青,郑涛,肖仕武,黄少锋,刘万顺.快速识别转换性故障的变压器差动保护新判据[J].电力系统自动化,2007,31(20):61-64.
作者姓名:杨青  郑涛  肖仕武  黄少锋  刘万顺
作者单位:华北电力大学电力系统保护与动态安全监控教育部重点实验室,北京市,102206
摘    要:电流互感器饱和是影响变压器差动保护可靠性的重要因素之一.传统的带比率制动特性的变压器差动保护在一定程度上提高了防止区外故障时保护误动的能力,但是如何及时处理区外转区内故障时保护的快速开放成为新的问题.文中提出一种简单的解除闭锁的方法,具体做法是,在选定的计算区域,利用变压器两侧电流综合负序分量的最大值与差动电流的综合负序分量进行比较,不仅能准确识别区内、区外故障,而且对于转换性故障也具有较好的识别能力.ATP仿真实验验证了该方法的有效性.

关 键 词:变压器差动保护  转换性故障  综合负序分量  电流互感器饱和
收稿时间:2006/10/17 0:00:00
修稿时间:2006-10-172007-04-30

A New Criterion for Transformer Differential Protection to Rapidly Identify Transferring Faults
YANG Qing,ZHENG Tao,XIAO Shiwu,HUANG Shaofeng,LIU Wanshun.A New Criterion for Transformer Differential Protection to Rapidly Identify Transferring Faults[J].Automation of Electric Power Systems,2007,31(20):61-64.
Authors:YANG Qing  ZHENG Tao  XIAO Shiwu  HUANG Shaofeng  LIU Wanshun
Affiliation:The Key Laboratory of Power System Protection and Dynamic Security Monitoring and Control Under Ministry of Education,North China Electric Power University,Beijing 102206,China
Abstract:Current transformer saturation has always been one of the major problems of degraded reliability of the transformer differential protection.The ratio restraining differential characteristic can enable the transformer protection to be immune to the mal-operation in the external fault to some extent.But how to unblock the differential protection rapidly for the transferring fault from an external one to an internal one has become a new problem.This paper presents a new method of unblocking the differential protection for the transferring fault.In the method proposed,current comparison is made between the maximal value of the integrated negative phase sequence component of the current on the two sides of a transformer and the integrated negative phase sequence component of the differential current.Based on the current comparison results,the method proposed can not only accurately identify the internal fault and the external one,but also the transferring fault developed from the external fault to the internal one.Simulation results of ATP validate the effectiveness of the method proposed.
Keywords:transformer differential protection  transferring fault  integrated negative phase sequence component  current transformer saturation