Proposals for an improvement in transformer diagnosis usingdissolved gas analysis (DGA) |
| |
Authors: | Kan H Miyamoto T |
| |
Affiliation: | Optec Dai-Ichi Denko Co. Ltd., Tokyo; |
| |
Abstract: | The diagnosis of oil-immersed transformers using the dissolved gas analysis (DGA) technique has been well accepted and widely used. IEC Publication 599 touches on the diagnosis of faults involving paper insulation based on the ratio of CO2/CO. It states that a fault involving paper insulation is probable when the CO2/CO ratio is 3 or lower; we would like to propose a figure of 10 |
| |