基于操作过电压作用35kV干式空心电抗器故障原因分析 |
| |
引用本文: | 张小平,刘小波,吴冬文,黄斌,吴花.基于操作过电压作用35kV干式空心电抗器故障原因分析[J].江苏电器,2016(11):31-34. |
| |
作者姓名: | 张小平 刘小波 吴冬文 黄斌 吴花 |
| |
作者单位: | 国网江西省电力公司检修分公司,江西 南昌,330029 |
| |
摘 要: | 结合电抗器的运行环境、投切过程及本身材质结构,介绍了一起35 k V电抗器闪络故障。通过对电抗器运行状态调查、故障设备检查、试验以及理论仿真分析,发现电抗器主要故障原因是断路器频繁投切过电压,在封包玻璃纤维结构不合理的电抗器首端线圈匝间绝缘层产生破坏。针对本次故障问题,提出相应防范措施,为今后电抗器绝缘选型、运行维护提供参考。
|
关 键 词: | 干式空心电抗器 故障分析 防范措施 |
Fault Analysis of 35kV Dry Air Reactor Based on Switching Overvoltage Impact |
| |
Abstract: | Combining with the operating environment of reactors, switching process and itself material structure, this paper introduced a case of 35kV reactors lightning fault. Analysis was made to reactors running status investigation, fault equipment inspection, testing and theoretical simulation. The main fault reason of reactors was the over-voltage during frequent switching between the reactor coils, which led to the turn-to-turn insulating layer damage of reactors head end coils with unreasonable package fiberglass structure. For this fault problem, this paper pro-posed the preventive measures, which provides references for the future reactors insulating model selection and operating maintenance. |
| |
Keywords: | dry air reactor fault analysis preventive measures |