基于操作过电压作用35kV干式空心电抗器故障原因分析
引用本文:张小平,刘小波,吴冬文,黄斌,吴花.基于操作过电压作用35kV干式空心电抗器故障原因分析[J].江苏电器,2016(11):31-34.
作者姓名:张小平  刘小波  吴冬文  黄斌  吴花
作者单位:国网江西省电力公司检修分公司,江西 南昌,330029
摘    要:结合电抗器的运行环境、投切过程及本身材质结构,介绍了一起35 k V电抗器闪络故障。通过对电抗器运行状态调查、故障设备检查、试验以及理论仿真分析,发现电抗器主要故障原因是断路器频繁投切过电压,在封包玻璃纤维结构不合理的电抗器首端线圈匝间绝缘层产生破坏。针对本次故障问题,提出相应防范措施,为今后电抗器绝缘选型、运行维护提供参考。

关 键 词:干式空心电抗器  故障分析  防范措施

Fault Analysis of 35kV Dry Air Reactor Based on Switching Overvoltage Impact
Abstract:Combining with the operating environment of reactors, switching process and itself material structure, this paper introduced a case of 35kV reactors lightning fault. Analysis was made to reactors running status investigation, fault equipment inspection, testing and theoretical simulation. The main fault reason of reactors was the over-voltage during frequent switching between the reactor coils, which led to the turn-to-turn insulating layer damage of reactors head end coils with unreasonable package fiberglass structure. For this fault problem, this paper pro-posed the preventive measures, which provides references for the future reactors insulating model selection and operating maintenance.
Keywords:dry air reactor  fault analysis  preventive measures