开口式电流互感器耐直流性能研究
引用本文:李敏,杨爱超,吴宇,靳绍平,朱亮,李东江.开口式电流互感器耐直流性能研究[J].电测与仪表,2019,56(13):123-128,135.
作者姓名:李敏  杨爱超  吴宇  靳绍平  朱亮  李东江
作者单位:国网江西省电力有限公司电力科学研究院,南昌,330096;国网江西省电力有限公司电力科学研究院,南昌,330096;国网江西省电力有限公司电力科学研究院,南昌,330096;国网江西省电力有限公司电力科学研究院,南昌,330096;国网江西省电力有限公司电力科学研究院,南昌,330096;国网江西省电力有限公司电力科学研究院,南昌,330096
基金项目:国家电网有限公司总部科技资助项目
摘    要:传统闭合磁路电流互感器易受直流分量影响引起磁饱和,导致测量误差非常大。定义了电流互感器耐直流性能的含义,从开口式电流互感器在考虑二次侧负载条件下的等效模型出发,分析了气隙长度对电流互感器有效磁导率和误差的影响,通过基于J-A模型从B-H磁滞回线分析了开口式电流互感器具有良好的耐直流性能。提出了基于比例直流叠加法的电流互感器耐直流性能检测方法,实验了气隙长度和直流分量对开口式电流互感器性能的影响。文中通过误差补偿使得开口式电流互感器兼顾耐直流性能和计量特性,为电流互感器在含直流分量负荷下准确计量提供理论基础。

关 键 词:开口式  电流互感器  耐直流性能
收稿时间:2018/5/15 0:00:00
修稿时间:2018/5/25 0:00:00

Research on Anti-DC Performance of Air-Gap-Core Current Transformer
LI Min,YANG Ai-chao,WU Yu,JIN Shao-ping,ZHU Liang,LI Dong-jiang,WANG Xun,TANG Xin-yu,LI Xin and NIE Fang-ming.Research on Anti-DC Performance of Air-Gap-Core Current Transformer[J].Electrical Measurement & Instrumentation,2019,56(13):123-128,135.
Authors:LI Min  YANG Ai-chao  WU Yu  JIN Shao-ping  ZHU Liang  LI Dong-jiang  WANG Xun  TANG Xin-yu  LI Xin and NIE Fang-ming
Affiliation:State Grid Jiangxi Electric Power Research Institute,State Grid Jiangxi Electric Power Research Institute,State Grid Jiangxi Electric Power Research Institute,State Grid Jiangxi Electric Power Research Institute,State Grid Jiangxi Electric Power Research Institute,State Grid Jiangxi Electric Power Research Institute,State Grid Jiangxi Electric Power Research Institute,State Grid Jiangxi Electric Power Research Institute,State Grid Jiangxi Electric Power Research Institute,State Grid Jiangxi Electric Power Research Institute
Abstract:The traditional closed magnetic circuit current transformer is liable to be influenced by DC component, resulting in magnetic saturation. Anti-DC performance of current transformer is defined in this paper. Based on the equivalent model of air-gap-core current transformer considering secondaly side load conditions, the influence of air gap length on effective permeability and error of current transformer is analyzed. the air-gap-core current transformer has good anti-DC performance from the B-H hysteresis loop based on the J-A model. A method of anti-DC performance of current transformers based on proportional DC superposition is proposed. The influence of air gap length and DC component on the performance of air-gap-core current transformer is tested. The ari-gap-core current transformer takes into account both anti-DC performance and metering characteristics by error compensation, it provides a theoretical basis for the accurate measurement of current transformer under DC load.
Keywords:air-gap-core  current transformer  anti-DC performance