基于自适应阻抗继电器的风电T接线路纵联保护方案
引用本文:郑涛,赵裕童,陈璨,李菁,王增平.基于自适应阻抗继电器的风电T接线路纵联保护方案[J].电力自动化设备,2018,38(2).
作者姓名:郑涛  赵裕童  陈璨  李菁  王增平
作者单位:华北电力大学新能源电力系统国家重点实验室,北京102206,华北电力大学新能源电力系统国家重点实验室,北京102206,国网冀北电力有限公司电力科学研究院,北京100045,华北电力大学新能源电力系统国家重点实验室,北京102206,华北电力大学新能源电力系统国家重点实验室,北京102206
基金项目:国家重点研发计划(973计划)资助项目(2016YFB0900600)
摘    要:风电的T型接入改变了系统拓扑和故障特性,导致继电保护整定与配合困难,传统距离保护应用于风电T接线路时存在适应问题。基于风电T接线路拓扑,分析了双保护方向对保护范围的影响,推导了测量阻抗表达式并提取了主要影响参数,指出风电的T型接入影响距离保护的动作性能;鉴于此,提出了基于自适应阻抗继电器的风电T接线路纵联保护方案。该方案实现了保护方向的唯一化,且保护动作区域能够根据过渡电阻、三端电源电势幅值比、相位差和风电电源等效序阻抗的变化进行自适应调整,提高了保护的可靠性和灵敏性。同时给出了自适应整定阻抗的具体计算方法,一定程度上降低了保护对通信系统的要求。仿真结果验证了所提保护方案的正确性和有效性。

关 键 词:继电保护  纵联保护  风电T接线路  适应性分析  测量阻抗  自适应阻抗继电器  计算方法
收稿时间:2017/1/6 0:00:00
修稿时间:2017/11/8 0:00:00

Pilot protection scheme for power transmission line with T-type wind power connection based on adaptive impedance relay
ZHENG Tao,ZHAO Yutong,CHEN Can,LI Jing and WANG Zengping.Pilot protection scheme for power transmission line with T-type wind power connection based on adaptive impedance relay[J].Electric Power Automation Equipment,2018,38(2).
Authors:ZHENG Tao  ZHAO Yutong  CHEN Can  LI Jing and WANG Zengping
Affiliation:State Key Laboratory for Alternate Electrical Power System with Renewable Energy Sources, North China Electric Power University, Beijing 102206, China,State Key Laboratory for Alternate Electrical Power System with Renewable Energy Sources, North China Electric Power University, Beijing 102206, China,Electric Power Research Institute, State Grid Jibei Electric Power Company Limited, Beijing 100045, China,State Key Laboratory for Alternate Electrical Power System with Renewable Energy Sources, North China Electric Power University, Beijing 102206, China and State Key Laboratory for Alternate Electrical Power System with Renewable Energy Sources, North China Electric Power University, Beijing 102206, China
Abstract:The T-type connection of wind power to the grid has changed the topology and fault characteristic of electric power system, bringing difficulties for relay protection setting and configuration. So there exists an adaptability problem when traditional distance relay is applied to power transmission line with T-type wind power connection. Based on the topology of power transmission line with T-type wind power connection, the influence of double protection direction on the protection range is analyzed. The measuring impedance expression is derived, and the main influencing parameters are extracted. It is pointed out that the T-type connection of wind power will affect the operating performance of distance protection, aiming at which, a pilot protection scheme for power transmission line with T-type wind power connection based on adaptive impedance relay is proposed. It has only one protection direction and its operation zone can be adaptively adjusted according to the variation of transition resistance, the amplitude ratio and phase difference of the three terminal electromotive forces and equivalent sequence impedance of wind power, which improves the reliability and sensitivity of the protection. Meanwhile, a calculation method of the impedance adaptive setting is given, which reduces the requirement of protection for communication system to a certain extent. Simulative results verify the correctness and validity of the proposed protection scheme.
Keywords:relay protection  pilot protection  power transmission line with T-type wind power connection  adaptation analysis  measuring impedance  adaptive impedance relay  calculation method