引用本文:王维俭,毕大强.防止高压厂用变压器低压侧单相接地造成发电机单相接地保护误动[J].电力自动化设备,2001,21(9):1-3.
作者姓名:王维俭  毕大强
作者单位:清华大学电机工程与应用电子技术系
摘    要:大型发电机应装设动作电压≥5V的基波零序电压(3U0)定子单相接地保护,但实际运行中,6kV厂用系统单相接地时,发电机侧基波零序电压高达13.2V和11.9V,造成发电机单相接地保护误动。误动原因是没有考虑高压厂用变压器耦合电容的传递零序电压,应该通过计算传递电压的大小,确定发电机3U0定子接地保护的动作电压值;或者为了获得动作死区≤5%的3U0定子接地保护,增设厂用系统零序制动电压。

关 键 词:变压器  低压侧单相接地保护  发电机  高压厂
文章编号:1006-6047(2001)09-0001-03
修稿时间:2001年6月18日

Preventing the Generator Stator Ground Protection from Maloperation Caused by the Secondary Ground Fault of High Voltage Station Transformer
WANG Wei-jian,BI Da-qiang.Preventing the Generator Stator Ground Protection from Maloperation Caused by the Secondary Ground Fault of High Voltage Station Transformer[J].Electric Power Automation Equipment,2001,21(9):1-3.
Authors:WANG Wei-jian  BI Da-qiang
Abstract:The large-sized generator ought to install the ground fault protection based on the zero-sequence fundamental voltage (3U 0)with the setting value not less than 5 V.But in the field operations,The 6 kV station service electrical system took place single-phase-to-ground faults reaulted in the zero-sequence fundamental voltages of generator reaching to 13.2 V and 11.9 V respectively,and the stator ground protection maloperated.Its reason lies in the zero-sequence transferring voltage caused by the coupling capacitance between primary and secondary windings of high voltage station transformer,which was not considered.The value of operating voltage 3U 0 should be set by calculation according to the transformer voltage,or the 3U 0 ground fault protection should extend the zero-sequence voltage of the station service electrical system as the restraint quantity for obtaining the operating dead-zone not more than 5%.
Keywords:ground fault protection  transferring voltage  zero-sequence fundamental voltage