纵联零序方向保护误动原因分析及其对策
引用本文:汪萍,陈久林.纵联零序方向保护误动原因分析及其对策[J].电力自动化设备,2007,27(7):122-125.
作者姓名:汪萍  陈久林
作者单位:1. 江苏电力调度交易中心,江苏,南京,210024
2. 江苏省电力试验研究院,江苏,南京,210036
摘    要:在非全相运行期间,由于保护逻辑设置不当或通道等因素的影响,往往会导致高压输电线路纵联零序方向保护误动作。结合现场500kV电网中出现的某次故障事故,深入分析了事故中纵联零序方向保护误动作的原因:通信接口设备对允许信号的展宽;非全相运行时没有闭锁纵联零序保护。并详细描述了影响纵联零序方向保护正确动作的主要因素,有弱馈、非全相运行、分布电容、功率倒向、零序互感等。给出了防止纵联零序方向保护误动作的解决措施:非全相运行与零序功率倒向、逻辑的输出通过或门构成闭锁纵联零序保护;去掉接口装置对允许信号的展宽。现场运行结果证明了该解决措施的准确性和有效性。

关 键 词:输电线路  纵联保护  零序  误动作
文章编号:1006-6047(2007)07-0122-04
收稿时间:2006-05-18
修稿时间:2006-05-182006-12-22

Analysis of longitudinal zero sequence direction protection misoperation and its countermeasures
WANG Ping,CHEN Jiu-lin.Analysis of longitudinal zero sequence direction protection misoperation and its countermeasures[J].Electric Power Automation Equipment,2007,27(7):122-125.
Authors:WANG Ping  CHEN Jiu-lin
Affiliation:1. Jiangsu Electric Power Dispatching Center,Nanjing 210024, China; 2. Jiangsu Electric Power Research Institute,Nanjing 210036,China
Abstract:If the protective logic setting is incorrect or the communication channel wrong,the longitudinal zero sequence direction protection of high voltage transmission line will operate improperly under non-complete phase operating condition.With an accident in 500 kV power network,an improper operation of the longitudinal zero sequence direction protection is analyzed:the enable signal is extended by the communication interface device and the longitudinal zero sequence protection is not blocked under non-complete phase operation.The main factors causing its improper operation are described in detail,i.e.week feeding,non-complete operation,distributed capacitance,inverse power direction,zero sequence mutual inductance,etc..The countermeasures are put forward:blocking the longitudinal zero sequence direction,protection by the OR gate output of the non-complete operation signal and inverse zero sequence power signal;removing the interface device to prevent extension of enable signal.Site operation shows that proposed countermeasures are correct and effect.
Keywords:transmission line  longitudinal protection  zero sequence  misoperation