首页 | 本学科首页   官方微博 | 高级检索  
     

自愈光学电流互感器现场运行稳定性试验
引用本文:于文斌,江 波,张国庆,王贵忠,申 岩,郭志忠.自愈光学电流互感器现场运行稳定性试验[J].电力自动化设备,2012,32(4):44-48,53.
作者姓名:于文斌  江 波  张国庆  王贵忠  申 岩  郭志忠
作者单位:1. 哈尔滨工业大学电气工程学院,黑龙江哈尔滨,150001
2. 四川电力科学研究院,四川成都,610072
3. 北京许继电力光学技术有限公司,北京,100094
4. 哈尔滨工业大学电气工程学院,黑龙江哈尔滨150001;北京许继电力光学技术有限公司,北京100094
基金项目:国家自然科学基金资助项目(11004040)
摘    要:从互感器误差校验、电能计量统计和电能计量系统整体校验3个方面对光学电流互感器的现场运行性能进行客观评价。投运前和运行中期的误差校验数据显示,变差小于0.1%,满足0.2S级要求。建立2套独立计量系统,在实际现场运行条件下进行长期数据比对,反映数字电能计量系统在各种环境因素影响下的长期运行稳定性。通过对数字电能计量系统的整体校验,在额定功率条件下不确定度达到9.0×10-5,置信概率达到97.15%,系统综合误差为1.013%,满足规程要求。

关 键 词:互感器  光学电流互感器  运行性能  电能计量  试验  误差分析  稳定性

Experiment on site operational stability of optical current transformer
YU Wenbin,JIANG Bo,ZHANG Guoqing,WANG Guizhong,SHEN Yan and GUO Zhizhong.Experiment on site operational stability of optical current transformer[J].Electric Power Automation Equipment,2012,32(4):44-48,53.
Authors:YU Wenbin  JIANG Bo  ZHANG Guoqing  WANG Guizhong  SHEN Yan and GUO Zhizhong
Affiliation:1,3(1.Department of Electrical Engineering,Harbin Institute of Technology,Harbin 150001,China; 2.Sichuan Electric Power Test & Research Institute,Chengdu 610072,China; 3.Beijing Xuji Power Optics Technology Co.,Ltd.,Beijing 100094,China)
Abstract:The site operational performances of optical current transformer are evaluated in error calibration,energy measurement statistics and metering system overall calibration.The error calibration data before and during site operation show the error change is less than 0.1 %,satisfying the requirement of class 0.2S.Two independent measuring systems are established for the long-term comparison of site operational data to demonstrate the long-term operating stability of digital energy metering system under various environmental conditions.The overall calibration data of digital energy metering system indicate that,at rated power,the uncertainty is 9.0 × 10-5,the confidence probability is 97.15 % and the system comprehensive error is 1.013 %,satisfying the requirements of codes.
Keywords:electric instrument transformers  optical current transformer  operational performance  electric power measurement  experiments  error analysis  stability
本文献已被 CNKI 万方数据 等数据库收录!
点击此处可从《电力自动化设备》浏览原始摘要信息
点击此处可从《电力自动化设备》下载全文
设为首页 | 免责声明 | 关于勤云 | 加入收藏

Copyright©北京勤云科技发展有限公司  京ICP备09084417号