基于分布参数模型的比相式单相故障单端测距算法
引用本文:林湘宁,黄小波,翁汉琍,鲁文军.基于分布参数模型的比相式单相故障单端测距算法[J].电网技术,2007,31(9):74-79.
作者姓名:林湘宁  黄小波  翁汉琍  鲁文军
作者单位:1. 三峡大学,电气信息学院,湖北省,宜昌市,443002
2. 华中科技大学,电力工程系,湖北省,武汉市,430074
摘    要:高压输电线路故障以单相接地短路为主,针对此类故障开展高精度的故障定位研究具有重要意义。基于集中参数模型的单端测距算法忽略分布电容的影响,在实际故障点距测量点较远时必然带来较大的误差。针对该问题文章提出了一种基于分布参数线路模型的电压、电流比相式单端测距算法,其原理为:通过相模变换与反变换估算出沿线各点故障相电压与相电流的分布,利用线路故障相残压与故障分量电流相位差最小的特征进行定位。该算法基于工频量,对采样率要求不高,大量的ATP仿真试验验证了该算法的有效性。

关 键 词:输电线路  单端故障测距  分布参数  比相  ATP仿真
文章编号:1000-3673(2007)09-0074-06
修稿时间:12 19 2006 12:00AM

A Novel Phase Comparison Algorithm for Single Terminal Fault Location Based on Distributed Parameter Model
LIN Xiang-ning,HUANG Xiao-bo,WENG Han-li,LU Wen-jun.A Novel Phase Comparison Algorithm for Single Terminal Fault Location Based on Distributed Parameter Model[J].Power System Technology,2007,31(9):74-79.
Authors:LIN Xiang-ning  HUANG Xiao-bo  WENG Han-li  LU Wen-jun
Affiliation:1. College of Electrical Engineering and Information Technology, China Three Gorges University, Yichang 443002, Hubei Province, China; 2. Department of Electrical Engineering, Huazhong University of Science and Technology, Wuhan 430074, Hubei Province, China
Abstract:Single-phase earth faults are in the majority of all faults occurred in EHV and UHV transmission lines,the research on accurate fault location of single-phase earth fault is significant.The lumped parameter model based single terminal fault location algorithm neglects the influence of distributed capacitance,so it brings bigger location error while fault occurs at a distant position.For this reason,the authors propose a distributed parameter model based single terminal fault location algorithm using phase comparison of voltage and current,that is,by means of phase and modular transformation and inverse transformation the distribution of voltage and current of faulty phase at all points along the line is estimated,then the fault is located according to the feature that at the faulty position the phase angle difference between the residual voltage and fault-component of current should be the least.The proposed algorithm uses power-frequency voltage and current only,so lower sampling rate is suitable and this algorithm can be easily implemented by existing protection devices.The effectiveness of the proposed algorithm is verified by a lot of ATP simulation results.
Keywords:transmission line  single terminal fault location  distributed parameter  phase comparison  ATP simulation