利用电流-电压导数线性度关系的小电流接地系统接地故障选线
引用本文:冯光,管廷龙,王磊,薛永端,俞小勇,徐丙垠.利用电流-电压导数线性度关系的小电流接地系统接地故障选线[J].电网技术,2021,45(1):302-311.
作者姓名:冯光  管廷龙  王磊  薛永端  俞小勇  徐丙垠
作者单位:国网河南省电力公司电力科学研究院,河南省郑州市450052;中国石油大学(华东)信息与控制工程学院,山东省青岛市266580;广西电网有限责任公司电力科学研究院,广西壮族自治区南宁市530023;山东理工大学智能电网研究院,山东省淄博市255049
基金项目:国家自然科学基金项目(51477184);国网科技项目“高渗透率分布式电源下配电网故障诊断与自组织控制技术研究”。
摘    要:更好地利用故障暂态与稳态信息,可以减少小电流接地故障选线算法复杂程度,提高适应性。分析了不接地与经消弧线圈接地系统发生单相接地故障时,不同出线暂态与稳态电气量的线性度关系,发现:健全线路的零序电流与母线零序电压导数之间始终呈正比例且比例系数为正;故障线路的零序电流与母线零序电压导数呈非线性关系或者比例系数为负的正比例关系。可对零序电流采样值序列与对应的母线零序电压差分值序列进行线性拟合,根据拟合优度及曲线斜率选择故障线路。方法可同时适用于不接地系统与谐振接地系统,且对高阻接地故障仍有较高的选线准确度,与以往的选线方法相比利用了更加丰富的故障电气量,提高了选线算法的适应性与选线的可靠性。仿真验证与现场数据验证了方法的正确性。

关 键 词:小电流接地系统  单相接地故障  故障选线  电流-电压导数线性度  线性拟合

Grounding Fault Line Selection of Non-solidly Grounding System Based on Linearity of Current and Voltage Derivative
FENG Guang,GUAN Tinglong,WANG Lei,XUE Yongduan,YU Xiaoyong,XU Bingyin.Grounding Fault Line Selection of Non-solidly Grounding System Based on Linearity of Current and Voltage Derivative[J].Power System Technology,2021,45(1):302-311.
Authors:FENG Guang  GUAN Tinglong  WANG Lei  XUE Yongduan  YU Xiaoyong  XU Bingyin
Affiliation:(State Grid Henan Electric Power Research Institute,Zhengzhou 450052,Henan Province,China;College of Information and Control Engineering,China University of Petroleum(East China),Qingdao 266580,Shandong Province,China;Electric Power Research Institute,Guangxi Power Grid Corporation,Nanning 530023,Guangxi Zhuang Autonomous Region,China;Smart Grid Institution,Shandong University of Technology,Zibo 255049,Shandong Province,China)
Abstract:A better use of the fault transient and the steady state information can reduce the complexity of the line selection algorithm for the non-solidly grounding faults and improve its adaptability.This paper analyzes the relationship between the transient or the steady electrical quantities of different lines when a single-phase grounding fault occurs between the ungrounded and the resonant grounding systems.It is found that there is a direct proportion between the zero-sequence current and the zero-sequence voltage derivative of the healthy line and the proportionality coefficient is always positive.And the relationship between zero-sequence current of the faulty line and the zero-sequence voltage derivative can either be non-linear or proportional and the proportionality coefficient is negative when the relationship is proportional.The sampled value sequence of zero-sequence current and voltage differential can be linearly fitted in order to select the faulty line according to the goodness of the fitting and the slope of the curve.This method can be applied to both the ungrounded and the resonant grounding systems at the same time,and it still has a high accuracy in the line selection for high impedance grounding faults.Compared with the previous line selection method,it utilizes more abundant fault electrical quantity,which improves the adaptability of line selection algorithm and the reliability of line selection.Simulation and field data verify the correctness of the method.
Keywords:non-solidly grounding system  single-phase grounding fault  fault line selection  current and voltage derivative linearity  linear fitting