首页 | 本学科首页   官方微博 | 高级检索  
     

华北电网广域实时动态监测系统
引用本文:李丹,韩福坤,郭子明,张黎,吕少坤,魏小伟,田枚,张雪轩,刘长银,肖晋宇,谢小荣,吴京涛,王立鼎,杨东,肖晓春.华北电网广域实时动态监测系统[J].电网技术,2004,28(23):52-56.
作者姓名:李丹  韩福坤  郭子明  张黎  吕少坤  魏小伟  田枚  张雪轩  刘长银  肖晋宇  谢小荣  吴京涛  王立鼎  杨东  肖晓春
作者单位:1. 华北电力调度局,北京市,宣武区,100053
2. 清华大学电机系,北京市,海淀区,100084
3. 北京四方继保自动化股份有限公司,北京市,海淀区,100085
摘    要:基于同步相量测量技术的电网实时动态监测系统能在线监测系统动态过程的全貌,同时,其记录的电网扰动事件数据有助于对仿真系统的模型与参数进行离线校核.文章结合华北电网实时动态监测系统的研制,论述了该系统的构成、主要功能和特点.该系统一期工程由华北网调主站系统和安装在7个关键发电厂和变电站的子站装置构成,子站与主站之间通过调度数据网连接.文章结合东北500kV系统三相短路大扰动试验介绍了该系统在华北电网中的实际应用情况.

关 键 词:广域测量系统(WAMS)  电网实时动态监测系统  电网动态过程  同步相量测量单元(PMU)  华北电网
文章编号:1000-3673(2004)23-0052-05
修稿时间:2004年11月9日

WIDE-AREA REAL TIME DYNAMIC SECURITY MONITORING SYSTEM OF NORTH CHINA POWER GRID
LI Dan,HAN Fu-kun,GUO Zi-ming,ZHANG Li,LU Shao-kun,WEI Xiao-wei,TIAN Mei,ZHANG Xue-xuan,LIU Chang-yin,XIAO Jin-yu,XIE Xiao-rong,WUJing-tao,WANG Li-ding,YANG Dong,XIAO Xiao-chun.WIDE-AREA REAL TIME DYNAMIC SECURITY MONITORING SYSTEM OF NORTH CHINA POWER GRID[J].Power System Technology,2004,28(23):52-56.
Authors:LI Dan  HAN Fu-kun  GUO Zi-ming  ZHANG Li  LU Shao-kun  WEI Xiao-wei  TIAN Mei  ZHANG Xue-xuan  LIU Chang-yin  XIAO Jin-yu  XIE Xiao-rong  WUJing-tao  WANG Li-ding  YANG Dong  XIAO Xiao-chun
Abstract:The full view of power system dynamic processes can be supervised by wide-area real time dynamic monitoring system (WAMS) based on synchronous phasor measurement (SPM) technology. Meanwhile, the recorded data of the power system disturbance accidents is helpful to the off-line verification of the model and parameters of simulation system. Based on the development of real-time dynamic monitoring system for North China Power Grid, the architecture, main functions and features of the monitoring system are described in detail. The first stage of this monitoring system consists of the master-station located at the dispatching center of North China Power Grid and the sub-stations installed in seven key power plants and substations; the connection among the sub-stations is implemented by dispatching data network. The practical application of this WAMS in North China Power Grid is presented through the artificial large disturbance test for three-phase short circuit occurred in Northeast China Power Grid.
Keywords:Wide-area measurement system (WAMS)  Power system real time dynamic monitoring system  Power system dynamic process  Phasor measurement unit ( PMU )  North China Power Grid
本文献已被 CNKI 维普 万方数据 等数据库收录!