首页 | 本学科首页   官方微博 | 高级检索  
     

基于光纤光栅传感器的变压器内部温度测量技术(英文)
引用本文:刘军,陈伟根,赵建保.基于光纤光栅传感器的变压器内部温度测量技术(英文)[J].高电压技术,2009,35(3):539-543.
作者姓名:刘军  陈伟根  赵建保
作者单位:State Key Laboralory of Power Transmission Equipment &. System Security and New Technology, Chongqing University, Chongqing 400030, China  
摘    要:Thermal modeling of the power transformer to estimate the internal temperature only reflects the winding hot spot to a certain extent. The application of optical fiber sensors to measure transformer internal temperature directly can obtain the true temperature with high accuracy and stability and overcome the shortcomings of traditional electric sensors. It analyses the measuring principle of FBG(fiber bragg grating)sensor, and constructs transformer internal temperature measurement platform with FBG temperature sensors, then adopt short-circuit method to simulate the process of winding heat under different load conditions. Finally the measurement of transformer internal temperature is conducted respectively with FBG temperature sensors and thermocouples. Comparison and analysis of the results shows that FBG sensors can effectively measure the internal temperature of the transformer.

关 键 词:FBG  sensor  hot-spot  temperature  power  transformer  temperature  measurement  winding  temperature  load  test

Measuring Technology of Transformer Internal Temperature Based on FBG Sensors
LIU Jun,CHEN Wei-gen,ZHAO Jian-bao,LIANG Ya-feng,ZHAO Xin.Measuring Technology of Transformer Internal Temperature Based on FBG Sensors[J].High Voltage Engineering,2009,35(3):539-543.
Authors:LIU Jun  CHEN Wei-gen  ZHAO Jian-bao  LIANG Ya-feng  ZHAO Xin
Affiliation:1. State Key Laboratory of Power Transmission Equipment & System Security and New Technology;Chongqing University;Chongqing 400030;China;2. Luoyang Power Supply Company;Henan 471000;China
Abstract:Thermal modeling of the power transformer to estimate the internal temperature only reflects the winding hot spot to a certain extent. The application of optical fiber sensors to measure transformer internal temperature directly can obtain the true temperature with high accuracy and stability and overcome the shortcomings of traditional electric sensors. It analyses the measuring principle of FBG(fiber bragg grating)sensor, and constructs transformer internal temperature measurement platform with FBG temperature sensors, then adopt short-circuit method to simulate the process of winding heat under different load conditions. Finally the measurement of transformer internal temperature is conducted respectively with FBG temperature sensors and thermoeouples. Comparison and analysis of the results shows that FBG sensors can effectively measure the internal temperature of the transformer.
Keywords:FBG sensor  hot-spot temperature  power transformer  temperature measurement  winding temperature  load test
本文献已被 CNKI 万方数据 等数据库收录!