首页 | 本学科首页   官方微博 | 高级检索  
     

一种基于单位功率因数控制的有源电力滤波器
引用本文:王建元,ZHANG Guo-fu,张国富,徐超,赵洪成.一种基于单位功率因数控制的有源电力滤波器[J].高电压技术,2007,33(9):138-142,183.
作者姓名:王建元  ZHANG Guo-fu  张国富  徐超  赵洪成
作者单位:1. 东北电力大学电气工程学院,吉林,132012
2. 国电吉林热电厂,吉林,132011
基金项目:东北电力大学博士基金资助项目(BSJXM-200401)~~
摘    要:为解决谐波污染、改善电能质量,采用基于单位功率因数的控制方法,提出了一种只需检测系统侧电流及逆变器直流电容电压,而无需实时检测、计算负载谐波电流,直接控制系统侧电流为与电网电压同相的标准正弦波的控制方法,其补偿电流的控制策略采用比例积分控制和三角波调制。按照H桥逆变器的单极性脉宽调制的主电路研制了一台高性能的5kVA单相有源电力滤波器实验样机。理论分析、仿真及实验结果证明该有源电力滤波器可同时实现补偿负载无功及谐波电流,控制简单且具有良好的动态性能。

关 键 词:有源电力滤波器  单位功率因数  无功补偿  比例积分控制  单极性脉宽调制  H桥
文章编号:1003-6520(2007)09-0138-05
修稿时间:2006-09-13

Active Power Filter by Unity Power Factor Control
ZHANG Guo-fu.Active Power Filter by Unity Power Factor Control[J].High Voltage Engineering,2007,33(9):138-142,183.
Authors:ZHANG Guo-fu
Affiliation:1. School of Electrical Engineering, Northeast Dianli University, Jilin 132012, China; 2. Jilin Thermal Power Plant, Jilin 132011, China
Abstract:A high performance single-phase active power filter(APF)was designed based on the unity power factor control.Without detecting and calculating the reactive current and harmonic current of the load,a new control method was proposed with which only the current of the power supply and the voltage of the DC capacitor of the inverter need to be detected,and the current of the power supply is made to be a standard sine wave with the same phase as the voltage of the source.The control strategies of compensation current are the PI control and the triangle wave modulation.The modulation of H-bridge inverter of the active power filter is unipolar Pulse Width Modulation(PWM).The performances of the single phase active power filter are analyzed in detail under steady and dynamic state.At last a 5 kVA laboratory apparatus is developed.The simulation and experiment results demonstrate that the active power filter can compensate the reactive component and harmonics of load current,its control is very simple,and the good real-time performance and dynamic performance are also verified by simulation and experiment.
Keywords:active power filter  unity power factor(UPF)  reactive power compensation  PI control  unipolar PWM  H-bridge
本文献已被 CNKI 维普 万方数据 等数据库收录!
设为首页 | 免责声明 | 关于勤云 | 加入收藏