首页 | 本学科首页   官方微博 | 高级检索  
     

10kV电容器组专用断路器控制回路优化设计
引用本文:崔勇,王川,牛满萍,代鑫波.10kV电容器组专用断路器控制回路优化设计[J].工矿自动化,2012,38(10):67-69.
作者姓名:崔勇  王川  牛满萍  代鑫波
作者单位:1. 华北电力大学经济与管理学院,北京102206;河南兰考供电公司,河南兰考475300
2. 江西吉安供电公司,江西吉安,343000
3. 中原工学院信息商务学院,河南郑州,450007
4. 华北电力大学经济与管理学院,北京102206;河南开封县供电公司,河南开封475100
摘    要:针对10kV电容器组断路器进行分合闸控制操作时经常发生断路器控制回路合闸线圈烧毁的问题,提出了一种断路器双合闸线圈控制回路的优化设计方案。该方案在原有的断路器合闸控制回路中增加了备用合闸控制回路,当主合闸线圈烧毁时,备用合闸线圈充电,合上断路器;备用合闸控制回路中串联了信号继电器,当主合闸线圈烧毁后信号继电器可发出故障信号,同时可保证备用合闸线圈端电压与主合闸线圈端电压保持一致。实际应用表明,该优化设计方案从根本上解决了断路器合闸线圈烧毁后不能及时合闸的问题,保证了电容器组的正常投退。

关 键 词:10kV电容器组  VS1型真空断路器  合闸控制  合闸线圈  信号继电器

Optimal Design of Control Loop of Special Breaker of 10 kV Capacitor Bank
CUI Yong , WANG Chuan , NIU Man-ping , DAI Xin-bo.Optimal Design of Control Loop of Special Breaker of 10 kV Capacitor Bank[J].Industry and Automation,2012,38(10):67-69.
Authors:CUI Yong  WANG Chuan  NIU Man-ping  DAI Xin-bo
Affiliation:1,5(1.School of Economy and Management of North China Electric Power University,Beijing 102206,China. 2.Henan Lankao Power Supply Company,Lankao 475300,China. 3.Jiangxi Ji’an Power Supply Company,Ji’an 343000,China. 4.College of Information and Business of Zhongyuan University of Technology,Zhengzhou 450007,China. 5.Henan Kaifeng County Power Supply Company,Kaifeng 475100,China)
Abstract:In view of problem that closing coil in control loop of breaker often happens burnout when breaker of 10 kV capacitor bank makes breaking-closing control operation,the paper proposed an optimal design scheme of double control loops of closing coil of breaker.The scheme adds standby closing control loop in original closing control loop of breaker.When main closing coil is burnout,standby closing coil is charged to close breaker.The standby closing control loop series signal relay which can send out fault signal after main closing coil is burnout and can ensure terminal voltage of standby closing coil is uniform with one of main closing coil.The actual application shows that the optimal design scheme solves problem that closing coil of breaker cannot close timely after it is burnout and ensures normal on/off of capacitor bank.
Keywords:10 kV capacitor bank  VS1 vacuum breaker  closing control  closing coil  signal relay
本文献已被 CNKI 万方数据 等数据库收录!
设为首页 | 免责声明 | 关于勤云 | 加入收藏