一种改进的矿井区域选择性联锁保护方案设计
引用本文:黄翠柏,唐白山. 一种改进的矿井区域选择性联锁保护方案设计[J]. 工矿自动化, 2012, 38(11): 43-46
作者姓名:黄翠柏  唐白山
作者单位:1. 郑州煤炭高级技工学校电气系,河南新郑,451150
2. 鹤壁煤业(集团)有限责任公司供电处,河南鹤壁,458000
基金项目:国家自然科学基金项目(51077125);河南省重点攻关项目(082102240008)
摘    要:针对井下综保开关因生产厂家不同和型号不同而存在的保护响应时间长、响应时间不确定等问题,在分析传统区域选择性联锁保护方案的基础上,提出了一种改进方案:将智能控制模块的开关闭锁信号接口串联在综保开关的脱扣信号回路中,采用1∶1霍尔型电流传感器从原保护装置的电流互感器的副边取电流信号作为智能控制模块采集的信号,直接通过电流传感器检测故障电流,使得各级保护响应不受综保开关的影响。测试表明,改进方案中智能控制模块的响应时间为800μs,明显优于传统方案。

关 键 词:煤矿供电网络  综保开关  越级跳闸  区域选择性联锁  短路保护  智能控制模块

Design of an Improved Protection Scheme of Mine Zone Selective Interlocking
HUANG Cui-bai,TANG Bai-shan. Design of an Improved Protection Scheme of Mine Zone Selective Interlocking[J]. Industry and Automation, 2012, 38(11): 43-46
Authors:HUANG Cui-bai  TANG Bai-shan
Affiliation:1.Electrical Department of Zhengzhou Advanced Coal Mining Technical School,Zhengzhou 451150, China.2.Power Supply Department of Hebi Coal Industry(Group) Co.,Ltd.,Hebi 458000,China)
Abstract:For problems that response time of underground integrated protection switches is long and uncertain because the switches are coming from different manufacturers and have different models,the paper proposed an improved protection scheme based on analysis of traditional protection scheme of zone selective interlocking: connect switch lockout signal interface of intelligent control module in tripping signal circuit of integrated protection switches in series,use 1:1 Hall-type current sensor to obtain current signal from secondary side of current transformer of the original protective device,and take the signal as acquisition signal of the intelligent control module.The scheme detects fault current through current sensor directly,which avoids protection from impact of integrated protection switches.The testing result shows that the intelligent control module in the improved scheme has response time of 800 μs,response speed is significantly improved compared with the traditional scheme.
Keywords:power supply network of coal mine  integrated protection switch  override trip  zone selective interlocking  short-circuit protection  intelligent control module