Measurement of thermal conductivity of ice slurry made from solution by transient line heat-source technique (analytical discussion on influence of latent heat of fusion) |
| |
Authors: | Koji Matsumoto Takahiro Suzuki |
| |
Affiliation: | aChuo University, Department of Precision Mechanics, 1-13-27 Kasuga, Bunkyo-ku, Tokyo 112-8551, Japan;bTakasago Thermal Engineering Co., Ltd., 4-2-8 Kandasurugadai, Chiyoda-ku, Tokyo 101-8321, Japan |
| |
Abstract: | We have been studying on ice slurry in a dynamic type ice storage system. The ice slurry has many good characteristics. The ice slurry can be made from a solution. When designing the ice storage system using this ice slurry, thermal conductivity of the ice slurry is essential.When thermal conductivity of the ice slurry made from a solution is measured by a transient line heat-source technique, a measurement value of thermal conductivity is affected by a latent heat of fusion of ice. Therefore, the thermal conductivity measured is apparent thermal conductivity. In this study, influences of Stefan number, initial concentration of the solution, initial solid fraction (initial IPF) and Fourier number on the thermal conductivity was analytically discussed to improve measurement accuracy of the thermal conductivity of ice slurry in the transient line heat-source technique. |
| |
Keywords: | Ice slurry Thermal storage Ice storage tank Process Measurement Thermal conductivityMots clé s: Coulis de glace Accumulation thermique Bac à glace Procé dé Mesure Conductivité thermique |
本文献已被 ScienceDirect 等数据库收录! |
|