首页 | 本学科首页   官方微博 | 高级检索  
     


Influence of ultrasound on pool boiling heat transfer to mixtures of the refrigerants R23 and R134A
Authors:Stefan Bonekamp  Konrad Bier
Affiliation:

Institut für Technische Thermodynamik und Kältetechnik, Universität Karlsruhe (TH), Karlsruhe, Germany

Abstract:The effect of ultrasound on pool boiling heat transfer to mixtures of the refrigerants R23 and R134a has been investigated in a wide range of heat flux and saturation pressure. The enhancement of the heat transfer coefficient, which can be achieved by ultrasound, is much more pronounced for mixtures than for pure substances. It is, however, limited to rather small heat fluxes (Image ). Especially remarkable is the fact, that the maximum influence of ultrasound on the heat transfer coefficient of the mixtures occurs at medium saturation pressures (p/pc ≈ 0.2); the effect is markedly less for higher and for lower saturation pressures. Obviously, the improvement of the heat transfer to mixtures is mainly caused by a decrease of the local saturation temperature near the heating wall, due to a better mixing in the liquid boundary. This explanation is supported by evaluating important parameters of bubble formation from high-speed photographs of the heating surface. It is further noticeable, that the well known hysteresis effect at the beginning of pool boiling is reduced to a great extent by exposure to ultrasound.
Keywords:heat transfer  mass transfer  pool boiling  refrigerant  mixture  R23  R134a  ultrasound  measurementtransfert de chaleur  transfert de masse  ébullition libre  frigorigène  mélange  R23  R134a  ultrason  mesure
本文献已被 ScienceDirect 等数据库收录!