Experimental validation of the simulation module of the water-cooled variable refrigerant flow system under cooling operation
Authors:Yue Ming Li  Jing Yi Wu  Sumio Shiochi
Affiliation:1. Institute of Refrigeration and Cryogenics, Shanghai Jiao Tong University, Shanghai, China;2. Daikin Industries, Ltd., 1304 Kanaoka-cho, Kita-ku, Sakai, Osaka 591-8511, Japan
Abstract:On the basis of EnergyPlus’s codes, the catalogue and performance parameters from some related companies, a special simulation module for variable refrigerant flow system with a water-cooled condenser (water-cooled VRF) was developed and embedded in the software of EnergyPlus, the building energy simulation program. To evaluate the energy performance of the system and the accuracy of the simulation module, the measurement of the water-cooled VRF is built in Dalian, China. After simulation and comparison, some conclusions can be drawn. The mean of the absolute value of the daily error in the 9 days is 11.3% for cooling capacity while the one for compressor power is 15.7%. At the same time, the accuracy of the power simulation strongly depends on the accuracy of the cooling capacity simulation.
Keywords:Energy simulation  Water-cooled variable refrigerant flow air-conditioning system  Cooling capacity  Compressor power  Validation