管板蒸发冷却式冷水(热泵)机组的适用性分析
引用本文:宋鹏远,石文星,王宝龙,张勇,钟惠安.管板蒸发冷却式冷水(热泵)机组的适用性分析[J].暖通空调,2019(4):27-36.
作者姓名:宋鹏远  石文星  王宝龙  张勇  钟惠安
作者单位:清华大学;广州华德工业有限公司
基金项目:"十三五"国家重点研发计划项目"长江流域建筑供暖空调解决方案和相应系统"(编号:2016YFC0700304);国家自然科学基金重点项目"利用自然环境低品位能源降低建筑供热空调能耗的理论和方法研究"(编号:51638010)
摘    要:以热源侧采用管板式换热器的蒸发冷却式冷水(热泵)机组为对象,采用实验及模拟相结合的方法,综合考虑防冻液的再生过程,建立了机组的性能模型,基于机组制热量是否适应建筑热负荷需求探讨了其适用性,并据此分析了其在典型城市办公建筑中的全年能耗、全年性能系数APF及一次能源利用率PER。结果表明:管板蒸发冷却式冷水(热泵)机组适用于我国夏热冬冷地区以及济南以南纬度较低的部分寒冷地区;在夏热冬冷地区办公建筑中APF在3.83~4.38之间,PER在1.10~1.26之间,而在济南以南纬度较低的寒冷地区办公建筑中APF在3.19~3.55之间,PER在0.92~1.02之间,且其PER均大于传统的水冷冷水机组+锅炉的冷热源方案。

关 键 词:管板式换热器  蒸发冷却  无霜空气源热泵  全年性能系数  一次能源利用率  冷水机组

Applicability analysis of tube-plate evaporatively-cooled water chilling (heat pump) packages
Song Pengyuan,Shi Wenxing,Wong Baolong,Zhang Yong,Zhong Huian.Applicability analysis of tube-plate evaporatively-cooled water chilling (heat pump) packages[J].Journal Heating Ventilating and Airconditioning,2019(4):27-36.
Authors:Song Pengyuan  Shi Wenxing  Wong Baolong  Zhang Yong  Zhong Huian
Affiliation:(Tsinghua University,Beijing,China)
Abstract:Taking the evaporatively-cooled water chilling(heat pump)packages using tube-plate heat exchanger on the heat source side as an object and considering the energy consumption of antifreeze solution regeneration,establishes the performance model of the packages using the methods of experiment and simulation.Conducts the applicability analysis of the packages by judging whether the heating capacity can meet the heating load demand.On this basis,analyses the annual energy consumption,annual performance factor(APF)and primary energy ratio(PER)of the packages in typical urban office buildings.The results indicate that tube-plate evaporatively-cooled water chilling(heat pump)packages are applicable in hot summer and cold winter zone and the part of cold zone south of Jinan.The APFs in office buildings in hot summer and cold winter zone are between 3.83 and 4.38,and the PERs are between 1.10 and 1.26.While the APFs in the part of cold zone south of Jinan are between 3.19 and 3.55 and the PERs are between 0.92 and 1.02.Its PERs are higher than that of conventional cold and heat sources using the water-cooled chiller and boiler.
Keywords:tube-plate heat exchanger  evaporative cooling  frost free air-source heat pump  annual performance factor  primary energy ratio  water chiller