水-水板式换热器运行故障原因及排除方法
引用本文:綦升辉,韩瑞香,种秋菊.水-水板式换热器运行故障原因及排除方法[J].煤气与热力,2007,27(4):74-75.
作者姓名:綦升辉  韩瑞香  种秋菊
作者单位:1. 山东理工大学,经济学院,山东,淄博,255000
2. 德州市热力公司,山东,德州,253000
摘    要:分析了热力站水-水板式换热器的运行故障,主要表现为:情况1,热流体出口温度达到冷流体出口温度的1.1倍以上;情况2,冷热流体出口温度接近且均偏低.情况1由于换热器内结垢导致热阻增大,可进行除垢、清洗排除故障.情况2由于换热器堵塞或一次侧进水管存在气堵,应加强施工管理,防止杂物进入管道;在一次侧进水管最高点安装放气阀,运行中经常放气.

关 键 词:水-水板式换热器  逆流传热  结垢  堵塞  板式换热器  运行故障  原因及排除方法  Heat  Exchanger  Plate  Methods  Removal  Causes  Malfunction  放气阀  中经  安装  最高点  管道  施工管理  加强  存在  进水管  一次侧  堵塞
文章编号:1000-4416(2007)04-0074-02
修稿时间:2006-11-192007-01-02

Running Malfunction Causes and Removal Methods of Water-Water Plate Heat Exchanger
QI Sheng-hui,HAN Rui-xiang,CHONG Qiu-ju.Running Malfunction Causes and Removal Methods of Water-Water Plate Heat Exchanger[J].Gas & Heat,2007,27(4):74-75.
Authors:QI Sheng-hui  HAN Rui-xiang  CHONG Qiu-ju
Affiliation:1. Economic College, Shandong University of Technology, Zibo 255000, China ; 2. Dezhou Heating Corporation, Dezhou 253000, China
Abstract:The running malfunction of water-water plate heat exchanger in substation is analyzed. It indicates with two cases, that in case one, the outlet temperature of hot fluid reaches over 1.1 times of that of cold fluid; in case two, the outlet temperatures of cold and hot fluids are alike and too low. For case one, the malfunction can be eliminated by descaling and cleaning because scaling in heat exchanger results in increasing of thermal resistance. For case two, the construction management should be rein- forced to prevent the entrance of foreign matter into pipeline because of the obstruction of heat exchanger or air blocking in intake water pipe on the high-temperature side. The air vent valve should be installed at the top of intake water pipe on the high-temperature side to vent air often during operation.
Keywords:water-water plate heat exchanger  countercurrent heat transfer  scaling  blocking