首页 | 本学科首页   官方微博 | 高级检索  
     


Estimating the germicidal effect of upper-room UVGI system on exhaled air of patients based on ventilation efficiency
Authors:Minki Sung  Shinsuke Kato
Affiliation:Institute of Industrial Science, The University of Tokyo, 4-6-1 Komaba, Meguro-ku, Tokyo 153-8505, Japan
Abstract:Upper room (UR)-ultraviolet germicidal (UVGI) systems, one of several disinfection applications of UV, target airborne infectious diseases in rooms of buildings such as healthcare facilities. Previous studies have introduced many experiments showing the germicidal effect of UR-UVGI systems. In this study, a novel numerical method of estimating the germicidal effect of UR-UVGI systems for air exhaled by ward patients was introduced. The method adopts and modifies the concept of ventilation efficiency because the germicidal effect depends upon how the air containing airborne infectious particles flows and stays within UV-radiated area. A case study based on a four-patient ward showed that UV doses were correlated with the age of the air exhaled by a source patient, as expected. Moreover, the UV doses were considerably affected by the position of the UR-UVGI system. Inactivation rates of the influenza virus estimated using the UV doses, were in the range of 48–74%, and those of Mycobacterium tuberculosis were 68–90% in the breathing area of a neighboring patient. The results indicate not directly the decreased concentration of airborne infectious particles, but the possibility of inactivation caused by the UR-UVGI system, which is useful for system optimization.
Keywords:Ultraviolet germicidal irradiation  Ventilation efficiency  Exhaled air  CFD
本文献已被 ScienceDirect 等数据库收录!
设为首页 | 免责声明 | 关于勤云 | 加入收藏