首页 | 本学科首页   官方微博 | 高级检索  
     


Above-floor tube-and-plate radiant floor model development and validation
Authors:SA Brideau  I Beausoleil-Morrison  M Kummert
Affiliation:1. CanmetENERGY, Natural Resources Canada, Ottawa, Canada;2. Department of Mechanical and Aerospace Engineering, Carleton University, Ottawa, Canada;3. Département de génie mécanique, école Polytechnique de Montréal, Montréal, Canada
Abstract:While some building energy simulation tools include dedicated models to represent thermally massive embedded-tubes radiant floor systems, there are no models available for lightweight above-floor tube-and-plate (AFTP) systems. AFTP systems consist of a grooved wooden subfloor (or high density insulation layer), and conductive fin. This paper discusses the development of a transient AFTP radiant floor model and its implementation into ESP-r. This AFTP radiant floor model uses the general approach of the existing embedded-tube model in ESP-r and combines an analytical model of the tube with a two-dimensional finite difference model of the top layers of the floor construction. The new AFTP radiant floor model was found to compare closely with a transient two-dimensional finite element analysis model. Additionally, a full-scale transient experiment was conducted to empirically validate the model. The new model's predictions were found to be in close agreement with the measurements from this experiment.
Keywords:Above-floor tube-and-plate radiant floor  model  experimental validation  inter-model comparison