首页 | 本学科首页   官方微博 | 高级检索  
     


Rogowski coil current transducer compensation method for harmonic active power error
Affiliation:1. Kirensky Institute of Physics, Siberian Branch, Russian Academy of Sciences, Krasnoyarsk 660036, Russia;2. Siberian State University of Science and Technology, Krasnoyarsk 660014, Russia;3. Institute of Engineering Physics and Radio Electronics, Siberian Federal University, Krasnoyarsk 660041, Russia
Abstract:In the harmonic active power measurement, the highest uncertainties are generally introduced by the current and voltage transducers. In a previous paper, the authors showed that the current transformer (CT) can introduce significant errors in such measurement, especially if the phase shift between voltage and current is close to ±90°. In such condition the errors on harmonic power measurement are mainly due to the CT phase displacement. This paper shows that better results can be achieved with more linear transducers, such as the Rogowski coil current transducers (RCCTs), whose metrological performance in distorted condition can be improved, by means of a proper compensation method. The proposed method for RCCTs compensation is based on the frequency response and it allows to reduce the errors on harmonic power measurement, also for phase shift close to ±90°. The study is supported by several experimental tests.
Keywords:Power system harmonics  Transducers  Current transformers  Frequency response  Power measurement  Rogowski coil
本文献已被 ScienceDirect 等数据库收录!
设为首页 | 免责声明 | 关于勤云 | 加入收藏

Copyright©北京勤云科技发展有限公司  京ICP备09084417号