首页 | 本学科首页   官方微博 | 高级检索  
     


Pressure Rises Due to Arc under Insulating Oil in Closed Vessel—Pressure Fluctuation of Depth Direction in Oil
Authors:TOMO TADOKORO  MASASHI KOTARI  TOSHIYA OHTAKA  MIKIMASA IWATA  TADASHI AMAKAWA
Affiliation:1. Central Research Institute of Electric Power Industry, Japan;2. Electric Power Engineering Systems Co., Ltd., Japan
Abstract:When a fault arc occurs in oil‐filled electric equipment, it generates a flammable gas and a dynamic pressure rise. In this study, the pressure rises due to the arc are measured in a closed vessel containing air and oil for different arc depths. The pressure rises in air and oil with different depth are measured under experimental conditions involving an arc current 6.6 kA, an arc duration of 100 ms. Experimental results show that the frequency of pressure fluctuation varies with the depth of the arc. Our approximate calculation of the pressure fluctuation with consideration of the oil flux is consistent with the experimental results.
Keywords:power equipment  arc  insulating oil  pressure rise  short‐circuit fault