针对双馈风电机组在电网电压不平衡及谐波畸变条件下的故障穿越问题,分析了此类电网故障对机组运行性能的影响,提出了一种双馈机组转子侧、网侧变流器的协同控制方案。通过改进转子侧、网侧变流器的矢量控制算法,抑制了双馈感应电机的电磁转矩波动,降低了机组输出总有功功率的波动,获得了对称、正弦的机组输出电流。仿真结果表明,所述控制方案能够显著改善双馈风电机组在此类电网故障条件下的运行性能,从而提高机组的故障穿越运行能力。  相似文献   

2.
Fault ride through (FRT) capability in wind turbines to maintain the grid stability during faults has become mandatory with the increasing grid penetration of wind energy. Doubly fed induction generator based wind turbine (DFIG-WT) is the most popularly utilized type of generator but highly susceptible to the voltage disturbances in grid. Dynamic voltage restorer (DVR) based external FRT capability improvement is considered. Since DVR is capable of providing fast voltage sag mitigation during faults and can maintain the nominal operating conditions for DFIG-WT. The effectiveness of the DVR using Synchronous reference frame (SRF) control is investigated for FRT capability in DFIG-WT during both balanced and unbalanced fault conditions. The operation of DVR is confirmed using time-domain simulation in MATLAB/Simulink using 1.5 MW DFIG-WT.  相似文献   