首页 | 本学科首页   官方微博 | 高级检索  
相似文献
 共查询到20条相似文献,搜索用时 15 毫秒
1.
This paper presents a steady-state model for predicting the performance of vapour-compression liquid chillers over a wide range of operating conditions. The model overcomes the idealisations of previous models with regard to modelling the heat exchangers. In particular, it employs an elemental NTU- methodology to model both the shell-and-tube condenser and evaporator. The approach allows the change in heat transfer coefficients throughout the heat exchangers to be accounted for, thereby improving both physical realism and the accuracy of the simulation model. The model requires only those inputs that are readily available to the user (e.g. condenser inlet water temperature and evaporator water outlet temperature). The outputs of the model include system performance variables such as the compressor electrical work input and the coefficient of performance (COP) as well as states of the refrigerant throughout the refrigeration cycle. The methodology employed within the model also allows the performance of chillers using refrigerant mixtures to be modelled. The model is validated with data from one single screw chiller and one twin-screw chiller where the agreement is found to be within ±10%.  相似文献   

2.
This paper is the second paper out of two which present the development of a dynamic model for single-effect LiBr/water absorption chillers. The first part describes the model in detail with respect to the heat and mass balances as well as the dynamic terms. This second part presents a more detailed investigation of the model performance, including performance analysis, sensitivity checks and a comparison to experimental data. General model functionality is demonstrated.A sensitivity analysis gives results which agree very well to fundamental expectations: it shows that an increase in both external and internal thermal mass results in a slower response to the step change but also in smaller heat flow oscillations during the transient period. Also, the thermal mass has been found to influence the heat flow transients more significantly if allocated internally. The time shift in the solution cycle has been found to influence both the time to reach steady-state and the transients and oscillations of the heat flow. A smaller time shift leads to significantly faster response.A comparison with experimental data shows that the dynamic agreement between experiment and simulation is very good with dynamic temperature deviations between 10 and 25 s. The total time to achieve a new steady-state in hot water temperature after a 10 K input temperature step amounts to approximately 15 min. Compared to this, the present dynamic deviations are in the magnitude of approximately 1–3%.  相似文献   

3.
The existence of faults in vapour compression chillers plays a significant role in terms of energy efficiency loss, performance degradations, and even environmental implications. In this paper, a dynamic model-based fault detection technique suitable for real-time implementation is proposed. The main objective is to obtain a reliable and automated tool for fault detection in vapour compression chillers, which can be applied in steady-state or transient operation. The fault detection methodology is based on comparing actual and expected performance using an adaptative model and operating variables dynamic thresholds. The technique has been successful applied for on-line refrigerant leakage detection with experimental tests involving the artificial introduction of the fault in a laboratory vapour compression plant, showing the results its capability of detecting incipient leakage failure conditions avoiding false alarms.  相似文献   

4.
为了模拟空调系统在部分负荷下的运行状况,提出了一种适于变工况下模拟的螺杆式冷水机组模型。根据基本的物理、流动和传热理论建立了由满液式蒸发器、壳管式冷凝器和压缩机子模型组成的水冷螺杆式冷水机组模型,然后利用FORTRAN语言进行编程并植入TRNSYS软件进行了模拟。结果表明,当冷负荷在100%-50%之间变化时,模拟COP值与实测COP值的相对误差在5%以内。这说明,本模型适于冷水机组在冷冻水流量、冷却水流量、冷负荷变化三参数变化下的模拟。  相似文献   

5.
随着冷水机组、单元式空调机和水源热泵机组等产品的能效指标从名义工况EER或COP发展到IPLV或ICOP,机组的变容量或变工况性能主要取决于压缩机的变容量或变工况性能。固定内容积比的螺杆式压缩机如果在偏离设计工况下工作,效率下降,进而导致整个机组的性能下降。本文研究变内容积比螺杆式压缩机,内容积比可变化,使得压缩机内压比与外压比与工况相适应,可提升压缩机效率及机组性能。应用于冷水机组、水源热泵机组时,水源热泵机组在制冷工况时能效比可提高14.1%~35%,冷水机组的IPLV可提高7.2%左右。  相似文献   

6.
The main purpose of this study is to investigate the performance of a transcritical CO2 cycle with an internal heat exchanger for hot water heating. Performance test and simulation have been carried out for a transcritical CO2 cycle by varying secondary heat transfer fluid temperatures at evaporator and gas-cooler inlets as well as the discharge pressure. Variations of mass flow rate of refrigerant, compressor power, heating capacity, and co-efficient of performance (COP) with respect to the length of an internal heat exchanger are presented at various operating conditions. Good quantitative agreement between model predictions and experimental results has been found; most parameters have absolute average deviations of less than 4%. As the length of the internal heat exchanger increases, COP is enhanced but heating capacity tends to decrease due to the trade-offs between the effectiveness and pressure drop in the internal heat exchanger.  相似文献   

7.
In this work, an unsteady state analysis of the compression cycle of a small hermetic reciprocating compressor for domestic refrigeration was carried out. A specific one-dimensional model of the valves was developed and the mass and energy balances were applied to the refrigerant inside the cylinder to determine the mass, pressure and temperature behaviour and the heat and work transfer through the compression process. This analysis was inserted into a traditional steady state model of the compressor to evaluate the efficiency of the compression cycle and the performance of the compressor unit. The whole simulation code was validated against the experimental measurements carried out on a R134a commercial unit in a wide range of operative conditions: a fair agreement was found between predicted and measured performances. The simulation code can be a useful tool for the analysis, the design and the development of small hermetic reciprocating compressors for domestic refrigeration.  相似文献   

8.
A steady state simulation model has been developed to evaluate the system performance of a transcritical carbon dioxide heat pump for simultaneous heating and cooling. The simulated results are found to be in reasonable agreement with experimental results reported in the literature. Such a system is suitable, for example, in dairy plants where simultaneous cooling at 4 °C and heating at 73 °C are required. The optimal COP was found to be a function of the compressor speed, the coolant inlet temperature to the evaporator and inlet temperature of the fluid to be heated in the gas cooler and compressor discharge pressure. An optimizing study for the best allocation of the fixed total heat exchanger inventory between the evaporator and the gas cooler based on the heat exchanger area has been carried out. Effect of heat transfer in the heat exchangers on system performance has been presented as well. Finally, a novel nomogram has been developed and it is expected to offer useful guidelines for system design and its optimisation.  相似文献   

9.
This paper presents a simple dynamic simulation model for predicting the evaporation rates of defrosted water from water trays in domestic refrigerators. The model was successfully tested for one domestic refrigerator. The model was used to investigate the effect of different variables (ambient temperature, relative humidity, air velocity, compressor heat, auxiliary condenser) by comparing eight different arrangements with each other on a consistent basis for effective evaporation of defrosted water. The model results indicate that the evaporation of water can be increased to the necessary rate by raising the water temperature and optimising the velocity of air over the water tray.

Résumé

Cette communication présente un modèle de simulation dynamique pour la prévision de la vitesse d'évaporation d'eau de dégivrage contenue dans les bacs de réfrigérateurs domestiques. On a utilisé ce modèle pour étudier les effets de diverses variables (température ambiante, humidité relative, vitesse d'air, chaleur dégagée par le compresseur et le condenseur auxiliaire) en comparant l'évaporation de l'eau de dégivrage dans huit dispositions différentes. Lés résultats indiquent qu'on peut accélerer la vitesse d'évaporation par l'augmentation de la température de l'eau et l'optimisation de la vitesse de l'air passant au dessus du bac à eau.  相似文献   

10.
The performance of a twin screw compressor operating under wet (two-phase) compression conditions in an ammonia–water compression absorption heat pump cycle is investigated both theoretically and experimentally. The paper reports on the influence of the location of liquid intake or, depending what applies, injection angle and mass flow rate of the injected liquid on compressor performance. Labyrinth seals separate the oil-free process side from oil lubricated bearing housing. Labyrinth seals leakage is modelled and its impact on performance is theoretically and experimentally investigated. The need for liquid injection from the discharge side to obtain acceptable performance is discussed based on experimental results.  相似文献   

11.
This paper is the first of two which presents the development of a dynamic model for single-effect LiBr/water absorption chillers. The model is based on external and internal steady-state enthalpy balances for each main component. Dynamic behaviour is implemented via mass storage terms in the absorber and generator, thermal heat storage terms in all vessels and a delay time in the solution cycle. A special feature is that the thermal capacity is partly connected to external and partly to internal process temperatures.In this paper, the model is presented in detail. For verification, the model has been compared to experimental data. The dynamic agreement between experiment and simulation is very good with dynamic deviations around 10 s. General functionality of the model and a more detailed comparison with experimental data are presented in Part II of this paper.  相似文献   

12.
A stream analysis model was developed to simulate the behavior of accumulators and their influence on the automotive air conditioning (A/C) systems. It allows a comprehensive steady state simulation with a set of input conditions such as refrigerant vapor mass flow rate and pressure at the inlet of an accumulator. In this study, the refrigerant/oil mixture is R134a/PAG oil which are totally miscible, but could be any air conditioning refrigerant/oil, including carbon dioxide (CO2)/oil. The model accounts for all major effects inside the accumulator, such as friction, bends, sudden expansion, sudden contraction and heat exchange. The outputs are vapor quality, pressure and temperature at various positions of accumulator. In order to verify the mathematical model, experiments are performed in an experimental setup made up of real size automotive air conditioning components. The simulated results agree well with the experimental data. The simulation and experimental results show an important function of accumulators that is to determine the vapor quality into compressor, and thus has influence on the performance of whole automotive A/C systems.  相似文献   

13.
In a refrigerant compressor, improvement in performance such as reduction of various electrical and mechanical losses, reduction of gas leakage, better lubrication, reduction of suction gas heating etc. can be achieved by maintaining a low temperature rise inside the compressor. Proper selection and location of an internal over load protector relay, estimation of heat transfer coefficient and winding insulation coefficient are also vital in enhancing the performance. In this context it is necessary to understand the temperature distribution inside a compressor for an optimal design. In this paper, a numerical model has been created and a heat transfer analysis for a hermetically sealed reciprocating refrigerant compressor is presented. The temperature distribution inside the compressor has been obtained taking into consideration the various heat sources and sinks and compared with experimental results. The maximum temperature was observed at the rotor which was 427.5 K. The deviation of the predicted rotor temperature from that of experimental value is 5.5% only. A good agreement was found between experimental results and that predicted in the numerical analysis.  相似文献   

14.
Parametric studies on hermetic reciprocating compressors   总被引:1,自引:1,他引:0  
An advanced numerical simulation model for the thermal and fluid dynamic optimization of hermetic reciprocating compressors has been developed. The quality of the numerical solution has been verified by means of a critical analysis of the different sources of errors, and validated through an extensive experimental comparison. This work is focused on presenting different parametric studies of hermetic reciprocating compressors, based on the numerical simulation model developed. Results presented show the influence of different aspects (geometry, motor, valves, working conditions, etc.) on the basis of the meaningful non-dimensional parameters, which describe the compressor behaviour (volumetric and isentropic efficiency, coefficient of performance, etc.). The idea of this paper is to show the possibilities offered by the simulation model and its final objective, a better understanding of the thermal and fluid dynamic compressor behaviour to improve the design of these equipments.  相似文献   

15.
Emerging triple-effect LiBr–water absorption chillers operate at higher temperatures and pressures than traditional double-effect chillers. However, there is not enough data about thermodynamic properties of LiBr–water solutions at such high temperatures. Using recently measured data of vapor pressure and heat capacity, we have developed the equations which can calculate the vapor pressure, enthalpy and entropy of LiBr solutions at such high temperatures. The developed equations are valid from concentrations of 40–65 wt.% and also from temperatures of 40–210°C. These equations will be very helpful for the modeling and design of triple-effect LiBr–water chillers.  相似文献   

16.
A system design method of thermoelectric cooler is developed in the present study. The design calculation utilizes the performance curve of the thermoelectric module that is determined experimentally. An automatic test apparatus was designed and built to illustrate the testing. The performance test results of the module are used to determine the physical properties and derive an empirical relation for the performance of thermoelectric module. These results are then used in the system analysis of a thermoelectric cooler using a thermal network model. The thermal resistance of heat sink is chosen as one of the key parameters in the design of a thermoelectric cooler. The system simulation shows that there exists a cheapest heat sink for the design of a thermoelectric cooler. It is also shown that the system simulation coincides with experimental data of a thermoelectric cooler using an air-cooled heat sink with thermal resistance 0.2515°C/W. An optimal design of thermoelectric cooler at the conditions of optimal COP is also studied. The optimal design can be made either on the basis of the maximum value of the optimal cooling capacity, or on the basis of the best heat sink technology available.  相似文献   

17.
This paper is the second part of our study on the advanced energy storage system using H2O–LiBr as working fluid. In the first part, the system working principle has been introduced, and the system dynamic models in the operation process have also been developed. Based on the previous research, this paper focuses on the numerical simulation to investigate the system dynamic characteristics and performances when it works to provide combined air-conditioning and hot water supplying for a hotel located near by Yangzi River in China. The system operation conditions were set as follows: the outdoor temperature was between 29 °C and 38 °C, the maximum air-conditioning load was 1450 kW, the total air-conditioning capacity was 19,890 kWh and the 50 °C hot water capacity for showering was 20 tons which needed heat about 721 kWh on a given day. Under these conditions, the system operation characteristics were simulated under the full- and partial-storage strategies. The simulation results predicted the dynamic characteristics and performances of the system, including the temperature and concentration of the working fluid, the mass and energy in the storage tanks, the compressor intake mass or volume flow rate, discharge pressure, compression ratio, power and consumption work, the heat loads of heat exchanger devices in the system and so on. The results also showed that the integrated coefficient of performances (COPint) of the system were 3.09 and 3.26, respectively, under the two storage strategies while the isentropic efficiency of water vapor compressor was 0.6. The simulation results are very helpful for understanding and evaluating the system as well as for system design, operation and control, and device design or selection in detail.  相似文献   

18.
Variable speed control of compressors is one of the best methods to regulate the capacity of heat pumps and air conditioners. An analysis is conducted for modeling the variable speed compressor for simulation of inverter air conditioner and heat pump. Having scattered the real operation performance of inverter compressor into infinite operation performance of constant speed compressor, the map-based method is utilized to fit the performance curves of inverter compressor. The model is built at the basic frequency and the map condition as the second-order function of condensation temperature and evaporation temperature. Then it is corrected by the compressor frequency as the second-order function of frequency and by the actual operating condition as the actual specific volume of the suction gas. This method is used to set up simulation models of three different compressors. Compared with the data provided by the compressor manufacturers, the average relative errors are less than 2, 3 and 4% for refrigerant mass flow rate, compressor power input and coefficient of performance (COP), respectively. This model of variable speed compressor is suitable for the simulation of inverter air conditioner and heat pump systems. Based on the experimental data and simulation model, the frequency at zero mass flow rate and power input at zero frequency are discussed and the relation between COP and compressor frequency is analyzed.  相似文献   

19.
Modeling of a domestic frost-free refrigerator   总被引:2,自引:0,他引:2  
In the present study, a comprehensive thermo-fluidic model is developed for a domestic frost-free refrigerator. The governing equations, coupled with pertinent boundary conditions, are solved by employing a conservative control volume formulation, in the environment of a three-dimensional unstructured mesh. Experiments are also conducted to validate the results predicted by the present computational model. It is found that the computational and experimental results qualitatively agree with each other, although certain discrepancies can be observed in terms of the exact numerical values obtained. For the freezer compartment, the computationally predicted temperatures are somewhat higher than the experimental ones, whereas for the refrigerating compartment, the computed temperatures are lower than the corresponding experimental observations. The difference between experimental and computational results may be attributed to the lack of precise data on the airflow rates and the unaccounted heat transfer rates through the door gaskets and the compressor. From the heat transfer and fluid flow analysis, certain modifications in the design are also suggested, so as to improve the performance of the refrigerator.  相似文献   

20.
Liquid refrigerant injection technique can be a very effective method for controlling subcooling and the compressor discharge temperature of a refrigeration system at high ambient temperatures. In this study, the effects of liquid refrigerant injection on the performance of a refrigeration system with an accumulator heat exchanger were investigated by varying the liquid injection rate at the conditions of constant expansion valve opening in the evaporator and constant total flow rate. During the tests, the ambient temperature was maintained at 43 °C. With the increase of the liquid injection rate, the subcooling at the inner heat exchanger outlet increased and the superheat at the accumulator outlet decreased. However, unacceptable results such as the increase of the compressor discharge pressure and decrease of the system performance were also observed depending on the control method applied. To obtain high system performance and reliability, optimum control methods for liquid injection in the accumulator heat exchanger are suggested. The liquid injection technique for the refrigeration system with an accumulator heat exchanger was found to be an effective method for controlling adequate subcooling and the compressor discharge temperature of the refrigeration system at high ambient temperatures.  相似文献   